A residual current device (RCD) is only useful if it trips when it should. Testing one with an instrument proves it disconnects fast enough, which a press of its test button can't. This guide covers what BS 7671:2018+A4:2026 requires, how to carry out the test, and what can catch you out. For how RCDs work and which type to choose, see RCD types explained.
What the test does
An RCD compares the current going out on the line with the current coming back on the neutral. The RCD tester, part of a multifunction tester (MFT), draws a set current from the line and returns it through the protective conductor instead of the neutral. To the RCD, that looks exactly like current leaking to earth through a fault or a person, so it trips, and the tester measures how long it took.
What BS 7671 requires
Since Amendment 2 (2022), the requirement is simple. Whatever the RCD's type (AC, A, F or B), its effectiveness is verified by a test with an alternating current at its rated residual operating current, IΔn:
- General (non-delay) RCDs, including all those giving additional protection at 30 mA: trip in 300 ms or less.
- S type (time-delayed) RCDs: trip between 130 ms and 500 ms. S types are used upstream for selectivity and can't be used for additional protection.
The tests at five times IΔn (40 ms) and half IΔn (should not trip), which older editions required, are no longer required. They are still useful for fault finding: a 30 mA device that trips at the half-rated test may be oversensitive, or the circuit may already have standing leakage. The instrument must meet BS EN 61557-6.
A healthy modern 30 mA RCD usually trips in well under 300 ms at IΔn, typically somewhere around 15 to 40 ms. A time close to the limit on a device that used to be fast is worth noting, even though it passes.
How to do the test
- Do the dead tests first. RCD testing comes after continuity of protective conductors, insulation resistance, polarity and earth fault loop impedance. The test current returns through the protective conductor, so it must be proven sound first. If it were broken, the tester would raise exposed metalwork towards line voltage while the test ran.
- Warn the occupants and plan for the trip. Every circuit on the RCD goes off. Think about computers, freezers, alarms and anything else that shouldn't lose power without warning.
- Disconnect loads where you can. Appliances that leak a little to earth add to the test current and make the RCD trip faster than it really would, hiding a slow device. Unplug what you can on the circuits it protects.
- Connect at the circuit side of the RCD. A socket on one of its circuits is convenient (a plug-in lead), or use flying leads on the outgoing terminals. Select the RCD's rated current and the "AC" waveform setting.
- Run the test and read the time. Most testers let you start the test at 0° or 180° on the waveform. Testing both and recording the longer time is common practice, though not a BS 7671 requirement.
- Press the test button. After the instrument test, operate the RCD's own test button to check its mechanism. Then reset the RCD and check everything has come back on.
Record the operating time in milliseconds, at IΔn, on the schedule of test results, and tick that the test button works.
Type A, F and B RCDs
Many testers have settings for Type A (a pulsed DC test current) and Type B (smooth DC). BS 7671 only requires the AC test for every type, so the AC setting is enough to show compliance. The other settings can be useful extra checks, for example when fault finding, but they aren't needed for the certificate.
S types and RCDs in series
Where a time-delayed S type RCD (say 100 mA) is upstream of 30 mA RCBOs, testing the S type through a circuit that has a 30 mA RCBO will trip the RCBO first, because it is faster and more sensitive. Test the upstream device at a point it protects directly, such as its own outgoing terminals or a circuit with no downstream RCD.
TT systems
In a TT installation, the RCD provides fault protection because the earth electrode resistance is too high for a fuse or circuit-breaker to clear a fault fast enough. BS 7671 requires RA × IΔn ≤ 50 V, where RA is the resistance of the earth electrode and protective conductors. For a 30 mA RCD that allows up to 50 ÷ 0.03 ≈ 1,667 Ω, but an electrode reading over about 200 Ω may not be stable over the seasons, and is worth improving. In a TT installation the RCD protecting the whole installation is critical: a failed main RCD on a TT system is coded C2 on an EICR. See EICR codes explained.
The test button and the user
The test button checks that the trip mechanism works by creating a small imbalance inside the device. It doesn't measure the trip time or prove the circuit's protective conductors are connected. BS 7671 asks for a notice at the consumer unit telling the user to press the test button every six months (it used to say quarterly). RCDs that are never operated can stick; pressing the button exercises the mechanism. A handy reminder is to do it when the clocks change.
When an RCD fails the test
- Doesn't trip at all. Check the tester's settings, that the circuit is really on that RCD, and its protective conductor is continuous. If it still won't trip, the device has failed and must be replaced.
- Trips too slowly. Retest with loads disconnected; then replace the device if it's still outside the limit.
- Trips as soon as the tester is connected, or at half-rated current. There may already be leakage on the circuits; an insulation resistance test or a leakage clamp will find out. See why does my RCD keep tripping.
Use the RCD test calculator to check a reading against the limits, and practise the whole test sequence in the inspection and testing simulator.
Going deeper
Where the old 40 ms and 300 ms figures come from
The RCD product standards (BS EN 61008-1 for RCCBs and BS EN 61009-1 for RCBOs) set the maximum break times: 300 ms at IΔn and 40 ms at 5 × IΔn for a general type, and 130 to 500 ms at IΔn for an S type. BS 7671 used to repeat these in Table 3A of Appendix 3. Amendment 2 deleted that table and reduced the field test to the single AC test at IΔn, on the reasoning that RCDs are tested in detail by their makers, and a simple, consistent field test is more useful than a range of tests that depend on the type and make.
Why connection angle matters
Some electromechanical RCDs respond slightly differently depending on whether the test current starts on the positive or negative half-cycle, because the residual magnetism in the core adds to one and opposes the other. Electronic RCDs (more common on RCBOs) are less sensitive to this. Testing both and recording the longer time gives the cautious figure.
Ramp tests
A ramp test raises the test current slowly until the RCD trips, showing the actual tripping current. The product standards require a general RCD to trip between 50% and 100% of IΔn, so a 30 mA RCD should trip somewhere between 15 and 30 mA. It's a useful check when an RCD trips for no obvious reason, along with measuring the standing leakage on each circuit.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- IET Wiring Matters issue 91 (July 2022), Michael Peace: Changes to RCD testing in BS 7671:2018+A2:2022
- IET: BS 7671 FAQs, consumer units and protective devices (six-monthly RCD test button notice, Regulation 514.12.2)
- BS 7671:2018+A4:2026 Regulations 643.7, 643.8 and 411.5.3: RCD verification and TT systems (IET, paid standard)
- BS EN 61557-6: equipment for testing, measuring or monitoring of protective measures, effectiveness of RCDs (paid standard)
- IET Guidance Note 3: Inspection and Testing (paid)