Inspection and testing cheat sheet ohmandtoken.com
Order of tests (as listed in the FICA Section C guidance)
- Visual inspection
- Continuity (protective conductors, then ring final circuits)
- Insulation resistance
- Polarity
- Earth fault loop impedance (Ze and Zs)
- Prospective fault current (PSCC and PEFC: record the higher)
- Additional protection by RCDs and RCBOs
- Phase rotation
- Functional testing
Insulation resistance (BS 7671 Table 64)
| Circuit | Test voltage (DC) | Minimum |
|---|---|---|
| SELV and PELV | 250 V | 0.5 MΩ |
| Up to 500 V (230 V and 400 V circuits) | 500 V | 1.0 MΩ |
| Above 500 V | 1000 V | 1.0 MΩ |
RCDs
- Test at IΔn: general RCDs trip within 300 ms; S type between 130 and 500 ms.
- ½ × and 5 × IΔn tests aren't required since Amendment 2.
- TT: RA × IΔn ≤ 50 V, so 1,667 Ω for 30 mA.
Continuity
- Low-resistance ohmmeter to BS EN 61557-4: at least 200 mA. Null the leads.
- Ring: r1 and rn within 0.05 Ω; r2 ≈ 1.67 × r1 for 2.5/1.5 mm²; each socket ≈ (r1 + r2) ÷ 4 after cross-connecting.
- R1+R2 per metre at 20 °C: 1.0/1.0 mm² 36.20 mΩ; 1.5/1.0 mm² 30.20 mΩ; 2.5/1.5 mm² 19.51 mΩ; 4.0/1.5 mm² 16.71 mΩ; 6.0/2.5 mm² 10.49 mΩ.
- Main bonding: in the order of 0.05 Ω or less.
Sources:
- BS 7671:2018+A4:2026 Part 6 and Table 64 (IET, paid)
- IET Guidance Note 3 (paid)
- SJIB FICA candidate guidance, Section C
Always check against your own copy of the current documents. Mains work must be carried out by a competent person.