Polarity testing explained: why it matters and how to test it

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

An Edison screw lampholder with its centre contact on the line and its screw thread on the neutral, a light switch in the line conductor, and a socket with the line on the right
Beginner

Polarity means having the line and neutral conductors connected the right way round everywhere in an installation. A circuit with reversed polarity usually works perfectly, which is exactly why it's dangerous: the fault is invisible until someone switches something off, thinks it's dead and touches it. This guide explains what has to be checked and how.

Why it matters

lineMCBswitch (line)neutralcentre contact = linescrew thread = neutral
Correct polarity: every single-pole device switches the line, and the line goes to the lampholder's centre contact.
  • Switches and fuses. A single-pole switch, fuse or circuit-breaker in the neutral disconnects the load, but leaves it connected to the line. With the light switched off, the lampholder, the flex and the fitting are still live. Someone changing a lamp or the fitting gets a shock.
  • Edison screw (ES) lampholders. The screw thread is the part you can touch while putting a lamp in. It must be the neutral, with the line on the centre contact.
  • Sockets and appliances. Appliances are designed to have their fuse, switch and thermostat in the line. A socket wired with line and neutral swapped puts the appliance's switched parts at line voltage when off, and an appliance's fuse would no longer be in the line conductor.
  • Protection. A circuit-breaker or fuse in the neutral can't protect against an earth fault from the line: the fault current goes round it.

What BS 7671 requires

Polarity is verified on every new circuit and every periodic inspection. The checks are that:

  • every fuse and single-pole control and protective device is connected in the line conductor only;
  • in circuits with an earthed neutral, Edison screw and centre-contact bayonet lampholders have their outer or screw contact connected to the neutral, so the centre contact is on the line (E14 and E27 lampholders to BS EN 60238 are exempt);
  • wiring is correctly connected to socket-outlets and similar accessories.

On a BS 1363 socket seen from the front, the earth is the top slot, the line is on the right and the neutral is on the left.

Testing polarity: dead tests first

Most polarity checking is done during the R1+R2 continuity test, with the circuit safely isolated:

  1. At the board, link the circuit's line conductor to its cpc with a short lead.
  2. At each point, measure between the line and earth terminals with a low-resistance ohmmeter. A low reading proves that terminal really is connected to the line conductor at the board, and gives R1+R2.
  3. Operate each switch while testing: with the switch on you should get a reading at the lampholder's line (centre) terminal; with it off, the reading should go open circuit. If the reading is unaffected by the switch, the switch is in the wrong conductor.
  4. On ring finals, the step 3 test of the ring final test (line and cpc cross-connected) proves polarity at every socket at the same time.

Check the neutral at each point as well: if line and neutral were swapped at an accessory, a line-to-cpc link would show continuity at the neutral terminal instead.

Live checks

  • At the origin, before energising. Confirm the supply polarity is correct with an approved voltage indicator: 230 V line to neutral and line to earth, close to 0 V neutral to earth. A DNO supply with reversed polarity is rare but does happen, and everything downstream would be wrong.
  • At each socket. When you measure Zs at a socket, the loop tester also shows whether the line and neutral are the right way round. Plug-in socket testers do the same, but they only check one socket at a time and can't detect some faults, such as a neutral and earth swapped behind the socket.

Three-phase: phase sequence

On a three-phase supply, the order the phases reach their peaks (L1, L2, L3) is the phase sequence or rotation. It decides which way three-phase motors turn. Check it at every three-phase outlet and distribution board with a phase rotation tester, especially after any work on the supply side. The ESQCR also forbid the network operator from changing the phase rotation of a supply without agreement, because of what it would do to customers' motors.

Where it goes wrong

Common polarity faults
FaultHow it's usually found
Switch wired in the neutral (old two-plate or loop-in wiring)R1+R2 at the lampholder unaffected by the switch; live voltage at the fitting with the switch off
Line and neutral swapped at a socketRing final step 3, loop tester at the socket, socket tester
Line and neutral swapped at the meter tails or main switchEvery circuit reversed; voltage indicator at the origin
Strapper and common confused on two-way switchingLight works from one switch only; continuity testing of the switch wiring

An incorrect polarity found on an EICR is coded C1 or C2 depending on whether danger is present now; see EICR codes explained. The inspection and testing simulator includes polarity faults to find.

Intermediate and advanced

Going deeper

Why E14 and E27 are exempt

E14 and E27 lampholders made to BS EN 60238 have to meet that standard's requirements for protection against touching live parts, including while a lamp is being screwed in, which is why BS 7671 exempts them from the polarity rule. Older lampholders and other sizes may not, so it remains good practice to wire every ES lampholder with the line on the centre contact.

Polarity on TN-C-S supplies

On a PME supply, the neutral and earth are joined in the supply cable. If the supply polarity were reversed at the cut-out, the installation's earthing terminal would be connected to the line, putting every exposed metal part at 230 V. That's why the origin check is done with a voltage indicator before the installation is energised, and why any doubt about supply polarity is reported to the DNO straight away.

Polarity of DC and PV circuits

On DC circuits, polarity also decides whether equipment works or is damaged. PV strings are checked for polarity at the combiner or inverter, string by string, before the DC isolators are closed, as part of BS EN 62446-1 testing; reversed strings in parallel can drive large currents through each other.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.