Variable speed drives (VSDs) explained: inverters, V/f, energy savings and safe installation

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A variable speed drive with its keypad display showing 40.0 Hz, wired by screened cable to an induction motor driving a fan. Cube law: 80 percent speed needs about 51 percent power
Beginner

A variable speed drive (VSD), also called an inverter, variable frequency drive (VFD) or AC drive, lets an ordinary induction motor run at any speed. It's now the usual way to start and control pumps, fans, conveyors and compressors. This guide explains how one works, why it saves energy, and what to watch when installing one.

What's inside

400 V50 HzRectifierdiodes: AC → DCDC bus≈ 560 V DCInverterIGBTs: DC → PWMsine insmooth DCPWM pulsesM
Rectify, smooth, then chop the DC back into AC at whatever frequency the motor needs.
  1. Rectifier. A bridge of diodes turns the incoming AC into DC.
  2. DC bus. Large capacitors smooth it. On a 400 V supply the bus sits at roughly the peak of the line voltage, 400 × √2 ≈ 566 V DC, a little less under load.
  3. Inverter. Six fast transistor switches (IGBTs) turn the DC on and off thousands of times a second. By varying the width of the pulses (pulse width modulation), the drive builds a current in the motor windings that follows a smooth sine wave at whatever frequency it chooses.

Speed, frequency and V/f

An induction motor's speed follows the supply frequency (see induction motors explained): a 4-pole motor runs near 1,500 rpm at 50 Hz and near 750 rpm at 25 Hz. But the drive can't just lower the frequency on its own: the motor's flux depends on volts per hertz, and at low frequency the full voltage would saturate the core. So the drive keeps the ratio constant. For a 400 V, 50 Hz motor that's 400 ÷ 50 = 8 V per Hz: at 40 Hz the drive supplies about 320 V. This is V/f control. Modern drives also offer vector (sensorless or closed-loop) control, which models the motor to give full torque even at very low speed.

Above the motor's base frequency the voltage can't rise any further, so the motor runs in "field weakening": faster, but with reduced torque. Running a standard motor well above 50 Hz also needs the maker's OK for its bearings and fan.

Why fans and pumps save so much

0%0%25%25%50%50%75%75%100%100%speedflow ∝ speedpressure ∝ speed²power ∝ speed³80% speed → 51% power
The affinity laws for centrifugal fans and pumps (ideal case, no static head).

For centrifugal fans and pumps, flow is proportional to speed, pressure to speed squared, and power to speed cubed. Running a fan at 80% speed needs only about 0.8³ ≈ 51% of the power. Throttling the flow with a damper or valve instead, with the motor at full speed, saves very little. That's why fitting drives to fans and pumps is one of the most reliable energy savings on a site. Pumps that lift water against a fixed height (static head) save less, because they need a minimum speed just to deliver any flow at all.

Setting up a drive

Before running a motor, enter its nameplate data: rated voltage, current, frequency, speed, power and power factor. Many drives then run an auto-tune to measure the motor. Then set:

  • Minimum and maximum frequency. Many motors can't cool themselves at low speed, because their fan is on the shaft.
  • Acceleration and deceleration ramps, in seconds. Too fast a deceleration on a high-inertia load makes the motor act as a generator, push the DC bus voltage up and trip the drive on overvoltage; a braking resistor or a longer ramp fixes it.
  • Motor overload: the drive's electronic thermal protection, set to the motor's full-load current.
  • Control source: keypad, terminals (start/stop and a 0 to 10 V or 4 to 20 mA speed reference) or a fieldbus.

Installing a drive

  • Screened motor cable. The fast-switching output is a strong source of electrical noise. Use the screened (armoured or braided) cable the maker specifies, terminated with 360° EMC glands at both ends, and keep it apart from signal and data cables.
  • Earth leakage. Drives have filters that leak current to earth, and a fault on the DC side can produce smooth DC fault current. An ordinary Type AC or Type A RCD may trip for no reason or be blinded by the DC. Follow the drive maker's instructions: many three-phase drives need a Type B RCD, or a supply without RCD protection where the rules allow. See RCD types and why does my RCD keep tripping.
  • Nothing between the drive and the motor that switches under load. An isolator at the motor for maintenance is fine, but it should only be operated with the drive stopped, or have an early-break auxiliary contact to stop the drive first. Never fit power factor correction capacitors on a drive's output.
  • Long motor cables can cause voltage spikes at the motor terminals from reflected waves. Check the maker's maximum cable length, and use output reactors or filters beyond it.
The DC bus stays charged. After a drive is isolated, its DC bus capacitors can hold a lethal charge for several minutes. Wait for the time printed on the drive (often 5 to 15 minutes), then measure the DC bus terminals with a suitable meter to prove it dead before working inside. The display going blank does not mean the capacitors are discharged.

Common faults

Typical drive trips and what they usually mean
TripUsual causes
OvercurrentAcceleration ramp too short, motor or cable fault, mechanical jam
DC bus overvoltageDeceleration too fast on a high-inertia load; no braking resistor; supply voltage high
UndervoltageSupply dip or a lost phase
Earth faultDamaged motor cable or winding insulation; test with the drive disconnected
Motor or drive overtemperatureRunning too slowly for too long, blocked cooling, overloaded

Never insulation-test a motor cable with the drive still connected: the test voltage can destroy its electronics. Disconnect the drive's output first.

The motor control simulator includes a drive circuit to wire, set up and fault find.

Intermediate and advanced

Going deeper

Harmonics from the rectifier

A six-pulse diode rectifier draws current in two pulses per half cycle, rich in 5th, 7th, 11th and 13th harmonics. On sites with many drives this distorts the supply voltage. DC link chokes or AC line reactors (often 3 to 5%) reduce it, and larger installations use 12-pulse, active front end or active filter solutions. ENA Engineering Recommendation G5 sets the harmonic limits for connections to UK networks.

Bearing currents

The fast voltage edges of PWM produce a common-mode voltage on the motor shaft. It can discharge through the bearings, pitting the races ("fluting") and causing early bearing failure, especially on larger motors. Remedies include proper high-frequency earthing with symmetrical screened cable, insulated bearings, shaft grounding rings and common-mode filters.

Regeneration

When a load drives the motor faster than the drive's output frequency, such as a lowering hoist or a decelerating fan, energy flows back into the DC bus. A braking chopper dumps it into a resistor as heat; regenerative (active front end) drives feed it back into the supply instead, which is worth it on lifts, cranes and test rigs.