The formulas
Power is voltage times current, with a power factor (PF) for AC loads that aren't purely resistive. Rearranged for current:
- DC:
I = P ÷ V - Single-phase AC:
I = P ÷ (V × PF) - Three-phase AC, balanced:
I = P ÷ (√3 × VL × PF), where VL is the line-to-line voltage (400 V in the UK) and I is the current in each line. √3 is about 1.732.
P is in watts, so multiply kW by 1,000 first. For kVA (apparent power) leave the power factor out: I = S ÷ V single-phase, or I = S ÷ (√3 × VL) three-phase. Going the other way, P = V × I × PF single-phase and P = √3 × VL × I × PF three-phase.
Common loads
| Load | Supply | Current |
|---|---|---|
| 3 kW immersion heater | 230 V single-phase | 13.0 A |
| 8.5 kW shower | 230 V single-phase | 37.0 A |
| 9.5 kW shower | 230 V single-phase | 41.3 A |
| 10.5 kW shower | 230 V single-phase | 45.7 A |
| 7.4 kW EV charger | 230 V single-phase | 32.2 A |
| 11 kW EV charger | 400 V three-phase | 15.9 A per line |
| 22 kW EV charger | 400 V three-phase | 31.8 A per line |
| 100 kVA transformer, full load | 400 V three-phase | 144.3 A per line |
These are at the stated voltage and a power factor of 1, apart from the transformer, which is rated in kVA. Use the rating plate for the real figure, especially for motors.
Which voltage to use
UK supplies are declared at 230 V single-phase and 400 V three-phase, and may lie between 6 % below and 10 % above that (216.2 V to 253 V for single-phase) under the Electricity Safety, Quality and Continuity Regulations. Most of the time the voltage you measure is around 235 to 245 V.
For a heater or shower (a plain resistance) the current goes up with the voltage, so use the voltage the appliance is rated at. Many showers are rated at 240 V: a 9.5 kW shower rated at 240 V draws 9,500 ÷ 240 = 39.6 A at 240 V, and at 230 V gives about 8.7 kW and draws about 37.9 A. Electronic loads such as EV chargers and switch-mode power supplies work the other way round: they hold their power, so the current rises a little as the voltage falls.
kW, kVA and power factor
kW is real power, the part that does work or makes heat. kVA is apparent power, simply volts times amps. They are linked by the power factor: kW = kVA × PF. Generators, transformers and UPS units are rated in kVA because their windings and cables are limited by current, whatever the power factor.
Heaters, kettles, ovens, showers and filament lamps have a power factor of 1, so kW and kVA are the same. Induction motors run at about 0.7 to 0.9 at full load, and lower when lightly loaded. Modern EV chargers and most good switch-mode supplies are close to 1. To raise a low power factor, see the power factor correction calculator.
Motors
The kW on a motor's rating plate is its shaft output, not what it draws from the supply. The supply has to provide the output plus the losses, so divide by the efficiency as well: I = Pout ÷ (√3 × VL × PF × η). For example, a 7.5 kW motor with a power factor of 0.85 and an efficiency of 90 % draws 7,500 ÷ (1.732 × 400 × 0.85 × 0.90) = 14.2 A.
This is a guide to the running current at full load. The full-load current on the rating plate is the figure to design with, and a direct-on-line motor takes several times its full-load current while it starts, so the protective device has to ride through that. You can wire, commission and fault find real motor starters in the motor control simulator, and three-phase power explained covers line and phase voltages.
From current to circuit
The current you work out here is the design current Ib. BS 7671 Regulation 433.1.1 requires Ib ≤ In ≤ Iz: the protective device rating In must be at least the design current, and the cable's current-carrying capacity Iz, after correction factors, must be at least the device rating. The calculator shows the smallest common MCB or RCBO rating at or above the current, but that is only the first step. Size the cable with the cable sizing calculator and check voltage drop, and for a whole installation use the maximum demand calculator. Note that BS 7671 allows no diversity on an EV charging final circuit.
On three-phase, the formula assumes the load is balanced across the three lines. For single-phase loads spread across a three-phase supply, add up the current on each phase separately.