The three-phase induction motor drives most of the world's pumps, fans, compressors and conveyors. It has no brushes, no commutator and, in its common squirrel cage form, no electrical connection to the rotating part at all. This guide explains how it works, what the nameplate tells you and how to connect one.
How it works: a rotating magnetic field
The stator (the fixed outer part) has three sets of windings, one for each phase, spaced around the frame. Because the three supply currents peak one after another, a third of a cycle apart, the magnetic field they make together rotates smoothly around the stator, without anything moving.
The rotor in a squirrel cage motor is a stack of steel laminations with aluminium or copper bars set in it, joined at each end by a ring, like a hamster wheel. The rotating field sweeps across the bars and induces currents in them, just as a transformer induces current in its secondary. Those currents make their own magnetic field, which is dragged round by the stator's field. That's the torque that turns the shaft.
Synchronous speed and slip
The field rotates at the synchronous speed, set by the supply frequency and the number of poles in the winding:
ns = 120 × f ÷ p (rpm, with f in Hz and p the number of poles)
| Poles | Synchronous speed | Typical full-load speed |
|---|---|---|
| 2 | 3,000 rpm | about 2,850 to 2,950 rpm |
| 4 | 1,500 rpm | about 1,420 to 1,480 rpm |
| 6 | 1,000 rpm | about 940 to 980 rpm |
| 8 | 750 rpm | about 700 to 740 rpm |
The rotor never quite catches up. If it turned at synchronous speed, the field wouldn't cut the bars, no current would be induced and there'd be no torque. The difference is the slip:
slip = (ns − n) ÷ ns
A 4-pole motor with 1,450 rpm on its nameplate has a slip of (1,500 − 1,450) ÷ 1,500 = 3.3% at full load. Slip rises with load, and is larger on small motors than big ones. A motor running noticeably slower than its nameplate speed is overloaded or has a supply problem.
Reading the nameplate
Everything you need to connect and protect the motor is on its rating plate:
- Power (kW): the output power at the shaft, not what it draws from the supply.
- Voltage and connection, for example 230 VΔ / 400 VY or 400 VΔ / 690 VY. The first value is for delta, the second for star.
- Current for each voltage: the full-load current (FLC) you set the overload to.
- Speed (rpm), frequency, power factor (cos φ), efficiency or IE class, duty (S1 = continuous), insulation class and IP rating.
Because the kW is output, the current comes from the input power:
I = P ÷ (√3 × V × power factor × efficiency)
A 7.5 kW motor on 400 V with a power factor of 0.85 and an efficiency of 89% draws 7,500 ÷ (1.732 × 400 × 0.85 × 0.89) ≈ 14.3 A at full load. Always use the nameplate current where you have it; the kW to amps calculator does the sum when you don't.
Star or delta?
The six winding ends come out to a terminal board, marked to IEC 60034-8: U1, V1, W1 along the bottom and W2, U2, V2 along the top. The order of the top row is offset on purpose, so the same straight links make either connection:
- In star, each winding gets the phase voltage: 400 ÷ √3 = 230 V on a 400 V supply.
- In delta, each winding gets the full line voltage: 400 V.
So match the nameplate to the supply. On a UK 400 V three-phase supply, a 230 VΔ / 400 VY motor is connected in star; a 400 VΔ / 690 VY motor is connected in delta, and is the kind that can use a star-delta starter. Connect a 230 VΔ / 400 VY motor in delta on 400 V and each winding gets √3 times its rated voltage: it draws far too much current and will burn out if the protection doesn't trip.
Direction of rotation
The motor turns in the direction the field rotates, which is set by the phase sequence. Swap any two supply lines and it runs the other way. That's how a forward/reverse starter works: two contactors, interlocked so both can never close, feeding the motor with two lines swapped. Check rotation on a new installation, uncoupled from its load if it matters, before handing over; a phase rotation tester checks the supply's sequence first.
Starting current and torque
At standstill the slip is 100% and the motor behaves like a transformer with its secondary shorted. Started direct on line, it typically draws about 5 to 8 times its full-load current until it gets up to speed. That's why motor circuits use Type C or D circuit-breakers, motor-rated fuses or motor circuit breakers that ride through the start, with a separate overload relay to protect against sustained overcurrent. On a weak supply, a big motor starting can dip the voltage for everyone else; reduced voltage starters (star-delta, soft starters) and variable speed drives reduce that.
Efficiency classes
Motor efficiency is graded by IEC 60034-30-1 from IE1 (standard) to IE4 (super premium) and IE5. Under the ecodesign rules in Great Britain (SI 2021/745, Schedule 16) and the EU (Regulation 2019/1781), most new three-phase motors from 0.75 kW to 1,000 kW must be at least IE3, and many from 75 kW to 200 kW must be IE4. When a motor runs most of the time, the electricity it uses in a year can cost more than the motor itself, so efficiency is worth paying for.
Testing a motor
With the motor safely isolated and locked off (see safe isolation) and the links removed:
- Winding continuity and balance. Measure U1–U2, V1–V2 and W1–W2 with a low-resistance ohmmeter. The three readings should be very close to each other. One noticeably different points to shorted turns or a bad connection.
- Insulation resistance. Test each winding to earth (the frame), and between windings, at a test voltage suited to the motor's rating (500 V DC for a 400 V motor). Disconnect drives and electronics first. Damp motors often read low and recover after drying out.
- Running checks. With the motor running, clamp the current in each line. It should be close to balanced and no higher than the nameplate FLC at full load. Unbalanced current with balanced voltages suggests a winding fault.
The motor control simulator lets you wire motors in star and delta, test windings and fault find on real circuits.
Going deeper
The torque-speed curve
An induction motor's torque isn't constant as it speeds up. It starts with the locked-rotor torque, often dips to a pull-up torque, rises to the breakdown (pull-out) torque near full speed, then falls steeply to zero at synchronous speed. The motor runs on the steep part, where a small rise in slip gives a big rise in torque, which is why its speed hardly changes with load. If the load torque exceeds the breakdown torque, the motor stalls. Design letters and NEMA/IEC designs (such as IEC design N and H) describe the shape.
Single phasing
If one line is lost while a three-phase motor is running, for example a blown fuse, it keeps turning on two lines but draws much more current in them, and overheats. It won't start from standstill on two lines; it just hums. Overload relays with phase-loss sensitivity trip faster on an unbalanced current to protect against this.
Power factor at light load
The current needed to magnetise the motor is roughly the same whether it is loaded or not, so a lightly loaded motor has a poor power factor and lower efficiency. Oversizing a motor "to be safe" wastes energy and adds reactive current. Capacitors at the motor, or a drive, can correct power factor; see the power factor correction lab.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- IEC 60034-8: rotating electrical machines, terminal markings and direction of rotation (U1, V1, W1 / U2, V2, W2; paid standard)
- IEC 60034-30-1: efficiency classes of line-operated AC motors (IE code; paid standard)
- The Ecodesign for Energy-Related Products and Energy Information (Amendment) Regulations 2021 (SI 2021/745), Schedule 16: electric motors (GB)
- Commission Regulation (EU) 2019/1781: ecodesign requirements for electric motors and variable speed drives (IE3 from 1 July 2021, IE4 for 75 to 200 kW from 1 July 2023)
- Wikipedia: Induction motor, synchronous speed, slip and starting current