Home / Learn / Power networks and motors

Motor starters explained: DOL, star-delta, contactors and overloads

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A DOL motor starter: in the panel an isolator Q1, a contactor K1 with coil terminals A1 and A2 and main terminals 1 to 6, and an overload relay F2 with contacts 95-96 and 97-98, all on a DIN rail; on the door a green start button, a black stop button and a red emergency stop on a yellow background
Beginner

A three-phase motor can't just be switched on with a big switch. It needs a starter: something to switch it on and off from push buttons, protect it from overload, and stop it restarting by itself after a power cut. This guide covers the two classic starters, direct-on-line (DOL) and star-delta, and how to read their circuits.

The parts of a starter

  • Isolator: a lockable switch to make the motor circuit dead for work. It is not for starting and stopping.
  • Short-circuit protection: fuses, a motor circuit breaker or a Type C/D MCB at the origin of the motor circuit, rated to ride through the starting current.
  • Contactor: a heavy-duty relay. A small control current through its coil (terminals A1 and A2) closes the main contacts (1-2, 3-4, 5-6) that switch the motor. Contactors for motors are rated by utilisation category AC-3, which covers starting a squirrel cage motor and switching it off while running.
  • Overload relay: thermal or electronic, it measures the motor current and opens its normally closed contact (95-96) if the current stays too high for too long. It doesn't break the main current itself: it drops out the contactor.
  • Control devices: stop and start push buttons, an emergency stop where needed, and indicator lamps.

Contactor and overload terminals are numbered to a standard scheme (EN 50005 / IEC 60947): main poles 1-2, 3-4 and 5-6 (often also marked L1-T1, L2-T2, L3-T3), normally open auxiliary contacts end in 3-4 (13-14, 43-44), normally closed ones in 1-2 (21-22, 31-32), and the overload's NC and NO contacts are 95-96 and 97-98.

Direct-on-line (DOL)

DOL is the simplest starter: the contactor connects the motor straight to the full supply voltage. The motor gets full starting torque, and draws its full starting current, typically 5 to 8 times FLC, for a few seconds. It suits most small and medium motors where the supply can take that current.

L (control)F3 control fuse9596F2 overload contact (NC)S1 stop (NC)S2 start (NO)1314K1 hold-inK1A1A2contactor coilN
The DOL control circuit, with the hold-in (latching) contact 13-14 across the start button.

How the control circuit works

  1. Press start (S2). Current flows through F3, the overload contact 95-96 and the stop button to the coil, and K1 closes.
  2. K1's auxiliary contact 13-14, wired across the start button, closes with it. When you let go of start, the coil stays energised through 13-14. This is the hold-in or latching contact.
  3. Press stop (S1), which is normally closed, and the circuit breaks: K1 drops out and its 13-14 opens, so it stays off when you let go.
  4. If the motor is overloaded, 95-96 opens and has the same effect as pressing stop.

The hold-in circuit gives no-volt protection for free. If the supply fails, the coil drops out and 13-14 opens. When power comes back, the motor stays off until someone presses start. BS 7671 and EN 60204-1 require precautions against a motor restarting unexpectedly where that could be dangerous, and this is the usual one. A maintained switch instead of push buttons would restart the motor the moment the power returned.

Setting the overload

On a DOL starter, set the overload to the motor's full-load current from the nameplate, for the voltage and connection it is running on. Overloads are made in trip classes. A Class 10 relay must trip in no more than 10 s at 7.2 times its setting, which suits normal motors; Class 20 and 30 allow longer starts for high-inertia loads such as large fans. An overload that trips during every start is either set wrong or the wrong class; one that never trips is no protection at all.

Star-delta starting

Star-delta reduces the starting current by starting the motor in star, then switching it to delta once it's up to speed. It only works with a motor that is designed to run in delta on the supply voltage: on a 400 V supply, a 400 VΔ / 690 VY motor with all six winding ends brought out (see induction motors explained).

L1L2L3K1 mainK2deltaF2 overloadset to 0.58 × FLCU1 V1 W1W2 U2 V2the six winding ends of the motorK3 starjoins W2, U2, V2K2 and K3 interlocked
Three contactors: K1 main, K3 star and K2 delta. The supply always reaches U1, V1 and W1 through K1.
  1. Start: K1 and K3 close. K3 joins W2, U2 and V2 into a star point, so each winding gets 400 ÷ √3 = 230 V.
  2. The timer runs, typically for a few seconds while the motor accelerates to near full speed.
  3. Changeover: K3 opens, then K2 closes. K2 connects each winding end to the next line (U1 to W2, V1 to U2, W1 to V2), making delta, and each winding now gets 400 V.

In star, each winding has 1 ÷ √3 of its voltage, so it draws 1 ÷ √3 of its current, and the line current is a further 1 ÷ √3 lower than in delta, where the lines feed two windings each. Together:

starting current in star = ⅓ of DOL    starting torque in star = ⅓ of DOL

That's the catch: a third of the torque. Star-delta suits fans, centrifugal pumps and machines that start unloaded. A motor that can't reach near full speed in star will draw a big current spike at changeover, which defeats the point.

Interlocks

K2 and K3 must never close together: that would short-circuit the supply through the delta contactor and the star point. Each has a normally closed auxiliary contact of the other in its coil circuit (an electrical interlock), and many have a mechanical interlock between them as well. The timer is arranged so K3 drops out before K2 can pick up.

Setting the overload in a star-delta starter

In the usual arrangement the overload sits after K1, in the lines that feed U1, V1 and W1. In delta, those lines carry the winding current, which is the line current ÷ √3. So set it to 0.58 × FLC: a motor with an FLC of 27 A in delta needs the overload set to 27 ÷ √3 ≈ 15.6 A. Check the starter maker's drawing: if the overload is in the incoming supply instead, it's set to full FLC.

Push button and lamp colours

EN 60204-1, the standard for machine electrical equipment, sets the colours:

  • Emergency stop: a red actuator on a yellow background, latching until reset (EN ISO 13850).
  • Start / on: white is preferred; grey, black and green are allowed. Red must not be used.
  • Stop / off: black is preferred; grey and white are allowed, and red is permitted but not close to an emergency stop. Green must not be used.
  • Indicator lamps: red = emergency, yellow = abnormal, green = normal, blue = action needed by the operator, white = neutral information.
Not the same as power switchgear. On UK distribution switchgear, the indicator convention is different: red means closed (on, live) and green means open (off). Don't carry one convention across to the other.

Soft starters and drives

A soft starter uses thyristors to ramp the motor's voltage up over a set time, giving a smooth start with lower current than DOL, and usually a soft stop too. It suits pumps (where it reduces water hammer) and conveyors. A variable speed drive (VSD, or inverter) changes the frequency as well as the voltage, so it can start a motor at full torque with little more than full-load current, and run it at any speed. Drives save a lot of energy on fans and pumps, but they bring their own issues: earth leakage that may need a Type B RCD, screened motor cables and EMC. See why does my RCD keep tripping for drive leakage.

Isolate before you touch. Pressing stop is not isolation: the contactor's incoming terminals are still live, and a control fault could pull it in. Isolate and lock off at the motor isolator, prove dead at the point of work, and remember control circuits may be fed from a separate supply.

Try it yourself

The motor control simulator starts with a single DOL starter and builds up to wiring a full star-delta panel from a drawing, then fault finding and commissioning it. Level 1 is free.

Intermediate and advanced

Going deeper

Open and closed transition

In a normal star-delta starter, the motor is briefly disconnected between K3 opening and K2 closing: an open transition. During that gap the rotor's field is still decaying, and when K2 closes the supply may be out of phase with it, giving a sharp current and torque transient. Closed transition starters add a fourth contactor and resistors to keep the motor energised through the changeover. They cost more and are used where the transient causes trouble.

Why the timer matters

Set the star time too short and the motor changes to delta while still slow, drawing a current close to its DOL value. Set it too long and the motor runs in star near full speed with only a third of the torque, so if the load rises it may slow down and overheat. Watch the current on a clamp meter during commissioning: the changeover should happen once the star current has fallen close to its running value.

Motor circuit and cable sizing

BS 7671 requires the conductors of a motor circuit to carry the full-load current, and the circuit to cope with the starting current. In a star-delta starter, the six cables to the motor each carry the winding current (0.58 × FLC) in delta, so they can be smaller than the supply cable. Check voltage drop during starting as well as running, because a big drop during a start can stop the motor accelerating.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.