On an AC supply, the current a load draws and the power it turns into useful work aren't always in step. Power factor measures how well they line up. It matters for cable and transformer sizes, for losses, and on business sites it can appear on the electricity bill. This guide explains it from the beginning.
Three kinds of power
- Real (active) power, P, in watts (W or kW): the power that does work, such as heat, light and turning a shaft.
- Reactive power, Q, in volt-amperes reactive (var or kvar): power that flows back and forth every half cycle to build up magnetic fields in motors and transformers, or electric fields in capacitors. It does no work, but it still takes current.
- Apparent power, S, in volt-amperes (VA or kVA): voltage times current, what the cables, switchgear and transformer actually have to carry.
For sine waves they form a right-angled triangle, and the power factor is the ratio of real to apparent power:
S² = P² + Q² power factor = P ÷ S = cos φ
where φ is the angle between the voltage and current waveforms. A heater has a power factor of 1: all the current does work. A lightly loaded induction motor might be 0.3 to 0.5; a fully loaded one is typically 0.8 to 0.9.
Lagging and leading
Inductive loads (motors, transformers, magnetic ballasts) make the current lag behind the voltage: a lagging power factor. Capacitive loads make the current lead: a leading power factor. Most sites are lagging because of their motors, which is why correction is done with capacitors: their leading reactive current cancels part of the motors' lagging reactive current.
Why it matters
For the same real power, a lower power factor means more current. A 50 kW three-phase load on 400 V draws 96.2 A at a power factor of 0.75 but only 76.0 A at 0.95. More current means:
- bigger cables, switchgear and transformers for the same useful power;
- more I²R loss in every cable: cutting the current from 96.2 A to 76.0 A cuts those losses by about 38%;
- more voltage drop;
- on larger business supplies with half-hourly metering, charges for excess reactive power from the network operator when the power factor falls below about 0.95.
Homes aren't charged for reactive power, so correcting the power factor of household appliances doesn't save money on a domestic bill, whatever some "energy saving" plug-in boxes claim.
Correcting power factor: a worked example
A workshop draws 50 kW at a power factor of 0.75 lagging. How much capacitance raises it to 0.95?
- At 0.75: S = 50 ÷ 0.75 = 66.7 kVA and Q = 50 × tan(cos⁻¹ 0.75) = 50 × 0.882 = 44.1 kvar.
- At 0.95: Q = 50 × tan(cos⁻¹ 0.95) = 50 × 0.329 = 16.4 kvar.
- Capacitors needed: 44.1 − 16.4 = 27.7 kvar. In practice you'd pick the next standard size up, such as 30 kvar, and check it doesn't push the power factor leading at light load.
QC = P × (tan φ1 − tan φ2)
The power factor correction calculator does this sum and gives the capacitance for single and three-phase, and the power factor correction lab lets you watch the current fall as you add capacitance.
Where the capacitors go
- At a single big motor, switched with it. Simple, and it reduces the current in the motor's own cable too. Don't oversize it: a capacitor larger than the motor's no-load reactive power can cause dangerous overvoltage (self-excitation) when the motor is switched off and still spinning. The overload setting may need to change if the capacitor is connected after it.
- At the main switchboard, as an automatic bank. A controller switches capacitor steps in and out to hold the target power factor as the load changes. This is the usual choice for a whole site.
Harmonics: when cos φ isn't the whole story
Electronic loads, such as LED drivers, computers and variable speed drives, draw current in short pulses rather than a smooth sine wave. That distorted current contains harmonics (multiples of 50 Hz) which add to the current without adding real power. The true power factor is then lower than the displacement power factor (cos φ) on its own. Ordinary capacitors don't fix distortion, and they can resonate with the supply at a harmonic frequency, overheat and fail. Sites with lots of drives use detuned capacitor banks with series reactors, or active harmonic filters.
Going deeper
Power factor with harmonics
True power factor = P ÷ (Vrms × Irms). With a sinusoidal voltage and a distorted current, it equals the displacement factor (cos φ of the fundamental) times the distortion factor, 1 ÷ √(1 + THDI²), where THDI is the current's total harmonic distortion. A six-pulse drive with a displacement factor near 1 can still have a true power factor of 0.7 or lower because of its harmonic current. DC link chokes or AC line reactors improve it.
Capacitance from kvar
For a single-phase capacitor, Q = V² × 2πfC, so C = Q ÷ (2πfV²). In a three-phase delta-connected bank, each capacitor sees the line voltage, so each one is C = Qtotal ÷ (3 × 2πf × Vline²). Star connection needs three times the capacitance for the same kvar, which is why banks are usually delta connected.
Resonance
A capacitor bank and the supply's inductance form a parallel resonant circuit. Its resonant frequency is roughly fr = f × √(Ssc ÷ QC), where Ssc is the short-circuit power at the busbar. If that lands near the 5th or 7th harmonic (250 or 350 Hz), harmonic currents from drives are amplified. Detuning reactors (often tuned to about 189 Hz, around a 7% reactor) move the resonance below the 5th harmonic.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- IEC 60050-131 (Electropedia): definitions of active, reactive and apparent power and power factor
- Wikipedia: Power factor, the power triangle, displacement and distortion power factor
- ENA Engineering Recommendation G5: harmonic voltage distortion limits for connections to UK networks (paid)