Steel wire armoured (SWA) cable is the standard choice in the UK when a cable has to be buried, run outside, or protected from damage: a supply to a garage, garden office or outbuilding, an EV charger on a driveway, or a sub-main across a factory. This guide covers how it's built, how to terminate it, how the armour is earthed, and what to check.
How SWA is built
From the inside out:
- Conductors: stranded copper.
- Insulation: usually XLPE (cross-linked polyethylene), rated for a conductor temperature of 90 °C. Older or some current types use PVC, rated 70 °C.
- Bedding: a layer that separates the cores from the armour.
- Armour: a layer of galvanised steel wires, which takes mechanical knocks and can be used as the circuit protective conductor (CPC).
- Outer sheath: black PVC for general use, or LSZH (low smoke, zero halogen) where fumes from a fire would be dangerous, such as escape routes and public buildings.
| Standard | Construction |
|---|---|
| BS 5467 | XLPE insulation, PVC bedding and sheath: the everyday "SWA" |
| BS 6724 | XLPE insulation with LSZH bedding and sheath |
| BS 6346 | PVC insulation, PVC sheath: an older type, rated 70 °C |
Core colours
Modern SWA uses harmonised colours: two-core is brown and blue; three-core is brown, black and grey (or brown, blue and green-and-yellow); four-core is brown, black, grey and blue; five-core adds green-and-yellow. If you use a core as the CPC, it must be green-and-yellow, or sleeved green-and-yellow at every end. In a three-core cable used for a single-phase circuit, for example, the grey core can't simply be used as an earth unless it's sleeved, and many installers choose a three-core with a green-and-yellow core instead. The cable colours cheat sheet has the full list.
Glands and terminating
SWA is terminated with a gland, which clamps the armour wires between a cone and a ring and grips the cable.
- A BW gland has no seal and is for indoor, dry places.
- A CW gland has a seal on the outer sheath, keeping water and dirt out. It's the usual choice outdoors and in damp places. A shroud over the gland adds protection.
- Specialist glands are used where the inner bedding also needs sealing, or in explosive atmospheres.
The armour must be connected to earth reliably. In a metal enclosure, the gland and an earth tag (often called a banjo) under its locknut connect it to the earth terminal. In a plastic enclosure there's no metal to bond to, so the earth tag and a green-and-yellow lead to the earth terminal are essential. Strip back only as much sheath as needed, and make sure the armour wires sit evenly in the cone.
Using the armour as the CPC
BS 7671 allows the steel armour to be the protective conductor, and it often is. But steel has a much higher resistance than copper, so you have to check two things:
- The earth fault loop impedance (Zs) at the end of the run is low enough for the protective device to disconnect in time. The armour's resistance adds to the loop.
- The armour's cross-sectional area is big enough to carry the fault current without overheating. Use the adiabatic equation:
S = √(I² × t) ÷ k
where I is the fault current, t the disconnection time and k a factor for the material (46 for steel armour on 90 °C XLPE cable, from BS 7671 Table 54.4). For example, a fault current of 500 A cleared in 0.4 s needs √(500² × 0.4) ÷ 46 = 6.9 mm² of armour. The manufacturer's data sheet gives the armour area for each cable size; check it's at least that. If it isn't, use a spare core as the CPC as well, or run a separate earth conductor.
On an outbuilding supplied from a TN-C-S (PME) house, think carefully before exporting the PME earth to the outbuilding, especially if it has a metal floor, a concrete floor with exposed steel, or outdoor equipment. Many installers make the outbuilding TT with its own earth electrode instead. If you do, the armour still has to be earthed at the house end, and must not connect the two earthing systems at the outbuilding end. See earthing systems.
Burying SWA
BS 7671 doesn't set a single burial depth. It requires buried cables to be armoured or in conduit or ducting, at a depth deep enough to avoid damage from foreseeable disturbance of the ground, and marked with cable covers or marker tape. In practice:
- Lay it deep enough that garden digging won't reach it, and deeper under driveways and fields.
- Lay marker tape above it, so anyone digging later finds the warning before the cable.
- Bed it in sand or fine soil, away from sharp stones.
- Duct it where it passes under paths and drives, so it can be replaced without digging up the surface.
- Record the route on a drawing with the installation's certificates.
- Don't bend it tighter than the manufacturer's minimum bending radius.
Sizing and testing
Size the conductors like any other circuit: the current rating for the way it's installed (buried direct, in a duct, clipped to a wall), then voltage drop over the length, then Zs and the protective conductor. Long runs to outbuildings are often set by voltage drop. The cable voltage drop calculator and cable sizing explained walk through it.
After installation, test continuity of every conductor including the armour, insulation resistance between all cores and between cores and armour, polarity, and Zs at the far end. A new circuit like this gets an Electrical Installation Certificate.
Going deeper
Why steel armour runs hotter in fault conditions
Steel has roughly eight times the resistivity of copper, so for the same cross-section it heats up much more quickly when fault current flows. The k factor in the adiabatic equation reflects this: 46 for steel armour against 143 for a copper core in the same type of cable. That's why a large-looking armour can still be too small for a high fault current.
Single-core SWA and AC
Single-core cables for AC use aluminium armour (AWA), not steel. Steel armour round a single conductor carrying AC would have large currents induced in it and get hot, because steel is magnetic. In multicore cables the currents in the cores cancel out, so steel is fine.
Aluminium conductors
Large sub-mains sometimes use aluminium-conductor SWA to save cost and weight. It needs a bigger conductor for the same current, terminals and lugs rated for aluminium, and care to stop corrosion at the joints.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 5467: Electric cables, thermosetting insulated, armoured, for 600/1000 V (paid standard)
- BS 6724: Electric cables, thermosetting insulated, armoured, low emission of smoke and corrosive gases (paid standard)
- BS 7671:2018+A4:2026 Regulation 543.1.3 and Table 54.4: adiabatic equation and k values for steel armour (IET, paid standard)
- BS 7671:2018+A4:2026 Regulation 522.8.10: buried cables (IET, paid standard)