"Turn it off" can mean four quite different things in electrical work. BS 7671 separates them, because the device that does one job safely may be dangerous if it's used for another. A light switch is fine for turning a light off, but you'd never rely on it to work on the light fitting.
The law: cutting off and isolation
The Electricity at Work Regulations 1989 (regulation 12) require suitable means, where necessary to prevent danger, for cutting off the supply to electrical equipment and for isolating it. The regulations define isolation as disconnecting and separating the equipment from every source of electrical energy in a way that is secure. BS 7671 Chapter 46 and Section 537 set out how installations meet that.
1. Isolation
Isolation cuts a circuit or installation off from every source of supply so that people can work on it safely. An isolating device must:
- have a big enough gap between its open contacts, so the supply can't jump across;
- show reliably when it's open, by a visible gap or a reliable indicator that only shows OFF when every contact is open;
- be capable of being secured in the off position, normally by a lock, so nobody can switch it back on while you're working;
- never be a semiconductor device, such as an electronic dimmer or a solid-state relay, because those don't create an air gap.
Devices that can be used for isolation include main switches and switch-disconnectors, isolators, circuit-breakers that are marked as suitable for isolation, fuses whose links are removed, and plugs and socket-outlets. An off-load isolator must not be opened while current is flowing; open the circuit with a switch first. Isolation is only half the job: you still have to prove it dead before you touch anything.
Whether the neutral must be isolated depends on the earthing system. In a TN-S or TN-C-S installation, the neutral normally doesn't need to be switched, because it is reliably connected to earth. In a TT system, the neutral must be isolated too, so the main switch has to be double-pole.
2. Switching off for mechanical maintenance
This is for non-electrical work on electrically powered equipment, like cleaning a machine, changing a fan belt or replacing a lamp, where the danger is the machine starting, moving or getting hot. The device should be in the main supply to the equipment, be clearly marked or obviously OFF when off, and be placed so it stays under the control of the person doing the work, or be lockable. A local isolator next to a motor or fan does this job. Typical examples are the isolator by an extractor fan or an air-conditioning unit outside.
3. Emergency switching and stopping
Emergency switching removes power as quickly as possible to remove an unexpected danger. The device must be easy to find and reach, act in a single operation directly on the supply, and be clearly identified: emergency stop buttons and handles are red against a contrasting background, normally yellow. Stop buttons latch in the off position, so releasing the button doesn't restart the machine. Machinery also needs emergency stopping, which stops movement as well as cutting power. On a machine controlled by a contactor, the emergency stop usually opens the contactor coil circuit: see motor control circuits.
4. Functional switching
Functional switching is ordinary control in normal use: light switches, dimmers, thermostats, timers and contactors. These devices don't need to isolate and can be semiconductor types. They can't be relied on for isolation or emergency switching unless they also meet those requirements.
Firefighter's switches
High-voltage signs and luminaires, such as neon signs, need a firefighter's switch, so firefighters can cut the supply before playing water on them. It's red, labelled FIREFIGHTER'S SWITCH, with the OFF position at the top, and placed where the fire service can reach it, normally outside next to the sign for an outdoor installation.
One device, several jobs
| Device | Isolation | Mechanical maintenance | Emergency | Functional |
|---|---|---|---|---|
| Switch-disconnector (main switch) | Yes | Yes | Yes | Yes |
| Off-load isolator | Yes | No (not on load) | No | No |
| Circuit-breaker marked for isolation | Yes | Yes | Yes | Yes |
| Fuse (links removed) | Yes | No | No | No |
| Plug and socket-outlet | Yes | Yes | No | Yes, up to 32 A |
| Contactor | Only if suitable and marked for isolation | Yes, if suitable | Yes | Yes |
| Semiconductor device (dimmer, SSR) | No | No | No | Yes |
Always check the manufacturer's marking and the requirements in BS 7671 Section 537 for the device in front of you, because the details depend on the product standard it was made to.
Going deeper
Isolating more than one source
Some equipment is fed from more than one place: a fitting supplied by two circuits, a machine with a separate control supply, or an installation with solar panels or a battery. Every source has to be isolated, and the equipment should carry a warning notice saying so. Remember that an inverter, a UPS or a capacitor can keep parts live after the mains is off.
Locking off properly
A lock only works if one person holds the only key. Use a personal lock and a multi-lock hasp when several people work on the same equipment, so it can't be switched on until the last person removes their lock. Add a warning notice. Where a circuit-breaker has no locking facility, a breaker lock-off clip is used.
Remote isolation
An isolator that's out of sight of the work, such as one in a plant room for a fan on the roof, must be lockable in the off position. If it isn't, a local isolator is needed at the equipment.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- The Electricity at Work Regulations 1989, regulation 12: means for cutting off the supply and for isolation
- BS 7671:2018+A4:2026 Chapter 46 and Section 537: isolation and switching (IET, paid standard)
- IET Guidance Note 2: Isolation and Switching (paid)