Motor control circuits explained: forward/reverse, interlocks, jog, two-station and sequence control

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A forward and reverse motor starter: two contactors K1 and K2 side by side with a mechanical interlock between them, with forward, reverse and stop push buttons
Beginner

Once you understand the basic start/stop circuit with its hold-in contact (see motor starters explained), most motor control circuits are built from the same few ideas: contacts in series mean all must be closed (AND), contacts in parallel mean any can be closed (OR), and normally closed auxiliary contacts stop two things happening at once. This guide works through the circuits you'll meet most often.

Forward and reverse

To reverse a three-phase motor you swap two of its supply lines (see induction motors). A reversing starter has two contactors: K1 feeds the motor L1-L2-L3, and K2 feeds it with two lines swapped, usually L1 and L3. If both ever closed together, they would short-circuit two phases. So the circuit is interlocked:

L (control) via F3, F2 95-96 and S1 stop1314fwd startK1 hold-in2122K2 (NC)K1forward1314rev startK2 hold-in2122K1 (NC)K2reverseNelectrical interlock: each NC 21-22 stops the other coil
Each contactor has its own start button and hold-in contact, and the other contactor's NC contact in its coil circuit.
  • Electrical interlock: a normally closed auxiliary contact (21-22) of K2 in K1's coil circuit, and of K1 in K2's. While K1 is in, K2's coil can't be energised, and the other way round.
  • Mechanical interlock: a lever fitted between the two contactors so they physically can't close together, even if a contact welds or someone pushes one in by hand. Reversing contactor pairs are usually sold with one fitted, and you should use both.
  • Push-button interlock (optional): each start button has a normally closed contact in the other direction's circuit, so pressing reverse first drops out forward. Use it only where reversing a running motor without stopping is acceptable: plugging a motor into reverse at full speed draws a very large current and stresses the machine and the contactors, which then need an AC-4 rating.

Jogging (inching)

A jog button runs the motor only while it is held, for positioning a machine. It energises the coil directly, without letting the hold-in contact latch. The simplest safe way is a jog button with two contacts: a normally open one that energises the coil, and a normally closed one in series with the hold-in path that breaks it while jog is pressed. Some circuits use a separate jog relay so the main contactor can never latch from a jog. Frequent jogging is a heavy duty for a contactor (AC-4), so check its rating.

Controlling one motor from two places

For start and stop at two stations, such as each end of a conveyor:

  • Stop buttons in series. Pressing any of them breaks the circuit.
  • Start buttons in parallel, and in parallel with the hold-in contact. Pressing any of them starts the motor.

The same rule extends to any number of stations. Emergency stops are always in series, and wired so they stop the machine directly, not through a programmable controller's software alone.

Sequence control

Conveyors feeding each other must start in order and stop in reverse order, or material piles up. If conveyor 1 (K1) carries away what conveyor 2 (K2) delivers, put a normally open auxiliary contact of K1 in series with K2's coil. K2 then can't start until K1 is running, and if K1 stops for any reason, K2 stops too. A timer (an on-delay contact) can add a gap between them so each conveyor is up to speed before the next starts.

Limit switches and other inputs

Any normally closed device in series with the coil acts like a stop button: a limit switch at the end of travel, a door interlock, a low-level float switch on a pump, or a pressure switch. Normally open devices in parallel with start act like start buttons, for example a float switch that starts a sump pump when the level rises. Safety-related inputs such as guard interlocks are designed to the machinery safety standards, with monitored, positive-opening contacts.

Why control circuits are earthed

control transformerfuseswitchescoilearthed sidefault to earth here:the fuse blows, the coilcan't be energised
With one side earthed and every switch on the other side, an earth fault can only blow the fuse.

EN 60204-1 requires that an earth fault in a control circuit can't start a machine or stop it being stopped. The usual way is to feed control circuits from a control transformer with one side of its secondary connected to the protective bonding circuit. The coils connect straight to the earthed side, and every switch, contact and button goes on the other side. If the switched wire faults to earth, the fault current flows straight to the earthed side and blows the control fuse, instead of finding a path round an open stop button to the coil. Common control voltages are 24 V DC, 110 V AC and 230 V AC.

Reading the drawing

  • Contacts are drawn in their de-energised, at-rest state.
  • Every contact carries the reference of the device it belongs to (K1, F2, S1) and its terminal numbers, so you can find it on the panel.
  • Cross-references under each coil list which page and column its contacts are on.
  • Wire numbers on the drawing match ferrules on the wires: follow the numbers, not the colours, when fault finding.

The motor control simulator has forward/reverse, sequence and timer circuits to wire from a drawing and fault find. Level 1 is free.

Intermediate and advanced

Going deeper

Safety functions and performance levels

Where a control function protects people, such as an emergency stop or a guard interlock, its reliability is assessed to BS EN ISO 13849-1 (performance levels PLa to PLe) or BS EN 62061 (SIL). Higher levels call for redundancy (two channels), monitoring (a safety relay that checks the contactors dropped out using their mirror contacts) and diagnostic coverage. A simple single-channel stop circuit may not be enough for a hazardous machine.

Stop categories

EN 60204-1 defines three stop categories: 0, immediate removal of power (uncontrolled stop); 1, a controlled stop with power available to the drive, then power removed; and 2, a controlled stop with power left on. An emergency stop must be category 0 or 1. With drives, category 1 lets the drive brake the load quickly before the safe torque off function removes power.

Mirror contacts

A mirror contact is a normally closed auxiliary contact guaranteed never to be closed at the same time as any main contact, even if a main contact welds. Safety relays monitor mirror contacts to detect a welded contactor and stop the machine being restarted.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.

  • BS EN 60204-1: safety of machinery, electrical equipment of machines (earthed control circuits clause 9.4.3, stop categories 9.2.2; paid standard)
  • IEC 60947-4-1: contactors and motor-starters (utilisation categories AC-3 and AC-4; paid standard)
  • BS EN ISO 13849-1: safety-related parts of control systems (performance levels; paid standard)