Safe isolation cheat sheet ohmandtoken.com
You need
- A two-pole voltage indicator to GS38 and BS EN 61243-3 (not a multimeter or non-contact tester).
- A proving unit.
- A lock, your own key, and a warning notice.
The steps
- Get permission and identify the circuit. Don't trust labels alone.
- Isolate, and check for other sources (PV, batteries, generators, UPS).
- Lock off, keep the key, fit a warning notice.
- Prove the indicator on the proving unit.
- Test dead at the point of work, every combination.
- Prove the indicator again.
- Start work. The lock stays on until you're finished.
Which conductors to test
| Supply | Tests | Number |
|---|---|---|
| Single-phase | L–N, L–E, N–E | 3 |
| Three-phase with neutral | L1–L2, L2–L3, L3–L1, L1–N, L2–N, L3–N, L1–E, L2–E, L3–E, N–E | 10 |
The law
- EAWR 1989 Regulation 12: means of cutting off and isolation.
- Regulation 13: precautions so equipment made dead stays dead.
- Regulation 14: no live working unless it's unreasonable for it to be dead, reasonable to work live, and suitable precautions are taken.
GS38 probes: no more than 4 mm of exposed tip, preferably 2 mm or less, with finger barriers.
Sources:
- Electricity at Work Regulations 1989 (legislation.gov.uk)
- HSE GS38
- Electrical Safety First Best Practice Guide 2
Always check against your own copy of the current documents. Mains work must be carried out by a competent person.