Somewhere near your home is a small fenced compound, a green steel kiosk or a transformer on a wooden pole. It's a distribution substation (also called a secondary substation), and it turns the 11,000 V distribution network into the 400 V and 230 V that homes and businesses use. A typical ground-mounted one supplies a few hundred homes. This guide explains what's inside and how it works.
The three main parts
- The ring main unit (RMU). Most urban 11 kV networks are built as rings: a cable runs from a primary substation, through a string of distribution substations and back to the same or another primary. The RMU has two ring switches, one for each direction, so either side can be switched out and the substation fed from the other. A third way, the tee-off, feeds the transformer through a fuse switch or a small circuit breaker that clears a transformer fault without tripping the whole ring. RMUs are usually insulated with oil or SF6 gas, or in newer designs with solid insulation or vacuum and dry air.
- The transformer. It steps 11 kV down to low voltage. The windings sit in a tank of mineral oil that insulates them and carries the heat to the cooling fins (cooling type ONAN: oil natural, air natural).
- The LV board. A busbar with several fused ways, each feeding a low voltage cable (a feeder) along one or more streets. The fuses are large BS 88 fuse links, sized for the feeder cable. Feeders from neighbouring substations are often joined at link boxes or pillars with the links left out: these are normally open points, which can be closed to back-feed a street when a substation or cable is out of service.
Ground-mounted and pole-mounted
| Ground-mounted | Pole-mounted | |
|---|---|---|
| Where | Towns, estates, industrial sites; in a kiosk, a brick building or a fenced compound | Rural areas on the overhead 11 kV network |
| Typical size | Several hundred kVA up to about 1,000 kVA | Much smaller, often well under 100 kVA |
| HV switching | Ring main unit | HV fuses on the pole (often drop-out expulsion fuses), switched from the line |
| Supplies | Hundreds of homes, through several LV feeders | A few farms or a handful of houses |
Pole-mounted transformers are often single-phase or split-phase on the most remote spurs; ratings and arrangements vary between network operators.
Why 433 V and not 400 V?
Distribution transformers are usually wound 11,000 / 433 V, so the open-circuit voltage between lines is 433 V (250 V line to neutral). Under load, voltage is lost in the transformer and the cables, so the customer at the far end of the feeder still gets a voltage inside the 230 V +10% / −6% limits. Most transformers also have an off-circuit tap switch, adjustable in steps of about 2.5% and only operated when the transformer is switched out, so the network operator can raise or lower the LV voltage to suit the area. You must never operate a tap switch on a live transformer.
Dyn11: what the code means
Every three-phase transformer has a vector group printed on its rating plate. On UK distribution transformers it is nearly always Dyn11:
- D: the 11 kV winding is connected in delta, so the HV side needs no neutral.
- y: the low voltage winding is connected in star.
- n: the star point (neutral) is brought out to a terminal, so loads can be connected line to neutral at 230 V and the neutral can be earthed.
- 11: the LV voltages lead the HV voltages by 30°, like the hour hand at 11 o'clock against the minute hand at 12.
The delta winding also lets third-harmonic currents circulate inside the transformer instead of flowing back into the 11 kV network, and it gives a path that keeps the LV voltages balanced when the load isn't. Two transformers can only be run in parallel if their vector groups, ratios and impedances match.
Currents in the numbers
The full-load current of a three-phase transformer is its rating divided by √3 times the line voltage. For a 500 kVA transformer:
I = S ÷ (√3 × V) = 500,000 ÷ (1.732 × 400) ≈ 722 A on the LV side
and 500,000 ÷ (1.732 × 11,000) ≈ 26.2 A on the 11 kV side. The same power at 11 kV needs about one twenty-eighth of the current, which is why the 11 kV cables are much smaller than the LV ones.
The transformer's impedance, a percentage on the rating plate, sets how much current flows in a short circuit on its terminals. With an impedance of 5%, the fault current is about full-load current ÷ 0.05, roughly 13 to 14 kA (the exact figure depends on whether you take the full-load current at 400 V or at the 433 V rating), if the 11 kV network behind it were infinitely strong. That's why LV fuses, link boxes and the switchgear near a big substation must have high breaking capacities, and why the prospective fault current at a service near a substation can be far higher than at the end of a long feeder.
Earthing at the substation
There are two earths at a distribution substation:
- The HV earth, which all the metalwork (tank, RMU, frames, fences) is bonded to. If an 11 kV conductor faults to the metalwork, this earth carries the fault current back to the source so the protection operates.
- The LV neutral earth, which earths the star point of the transformer. On PME networks the neutral is also earthed at many more points along the feeders.
During an HV earth fault, the earth electrode system's voltage rises above true earth (the rise of earth potential). If that rise is small enough, the HV and LV earths can be combined. If not, they are kept separate, so a high voltage can't be transferred along the neutral to customers' installations. Which applies to a given site is the network operator's design decision, based on measurements and calculations to ENA standards.
Try it yourself
In the LV switching simulator you move normally open points, phase out across a link box and isolate a feeder at the substation LV board. The HV switching simulator covers switching and earthing a ring main unit and issuing the safety documents.
Going deeper
Losses: iron and copper
A transformer has two kinds of loss. No-load (iron) loss is the energy needed to magnetise the core, and it is there all the time the transformer is energised, even with no load. Load (copper) loss is I²R heating in the windings and goes with the square of the load. At half load, copper loss is a quarter of its full-load value. Because distribution transformers spend most of their life lightly loaded, low no-load loss matters; the EU and GB Ecodesign rules for transformers set maximum losses for new units.
Loading in winter
Oil-filled transformers have a large thermal mass, so they can carry more than their nameplate rating for a few hours, especially in cold weather. Network operators use this when deciding how much load a substation can take, but the hottest spot in the winding sets the insulation's life, so the margins are calculated, not guessed.
Neutral current and unbalance
With single-phase loads, the three phases rarely carry equal current, and the neutral carries the difference. Heavy unbalance raises the voltage on the lightly loaded phases and lowers it on the busy one. Network operators rebalance by moving services between phases. The supply point testing simulator shows why a lost neutral on a three-phase feeder is so dangerous.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- ENA Technical Specification 35-1: distribution transformers, 11 kV and 6.6 kV to 433 V (paid)
- IEC 60076-1: power transformers, general (vector group notation and rating plates; paid standard)
- The Electricity Safety, Quality and Continuity Regulations 2002, regulation 27: declared voltage and permitted variations
- Wikipedia: Distribution network operator, the 14 GB licence areas (citing Ofgem); Electricity North West, Iberdrola ownership and the 2025 rename
- SSEN Distribution operational safety manual and network design documents (public extracts used by our HV and LV simulators)