The fuses and circuit-breakers in a consumer unit detect a fault and break the circuit in the same device. On high voltage networks the jobs are split: a current transformer measures the current, a protection relay decides whether there's a fault and how long to wait, and a circuit breaker does the switching when the relay tells it to. This guide explains how that works and the main types of relay you'll meet on UK networks.
From fault to trip
A current transformer (CT) around the conductor produces a small secondary current in proportion to the primary. A 400/1 CT gives 1 A at 400 A primary, and 10 A in a 4,000 A fault. Secondaries are rated 1 A or 5 A. The relay compares that current with its settings and, when it decides to trip, closes a contact that connects the substation's DC battery to the breaker's trip coil. The battery is there so the protection still works when a fault has pulled the AC voltage down.
Overcurrent protection and IDMT curves
The workhorse of distribution protection is the inverse definite minimum time (IDMT) overcurrent relay. The bigger the current, the faster it trips, down to a minimum time at very high currents. That lets relays further from the fault wait longer than relays close to it, so only the nearest breaker trips.
Modern numerical relays use the curves in IEC 60255-151, which came from the old British Standard BS 142:
t = TMS × k ÷ ((I ÷ Is)α − 1)
| Curve | k | α | Typical use |
|---|---|---|---|
| Standard inverse (SI) | 0.14 | 0.02 | General feeder protection, the most common in the UK |
| Very inverse (VI) | 13.5 | 1 | Where fault current falls a lot along the feeder |
| Extremely inverse (EI) | 80 | 2 | Grading with fuses, and riding through inrush and cold load pick-up |
| Long time inverse (LTI) | 120 | 1 | Standby earth fault on transformer neutrals |
- Is is the current setting (on older relays, the plug setting), in primary amps or as a percentage of the CT rating. Below it the relay doesn't time at all.
- TMS is the time multiplier setting. It slides the whole curve up or down: at TMS 0.5 every time is half what it is at TMS 1.
For a standard inverse relay at TMS 0.1, the operating time is 1.00 s at twice setting, 0.43 s at five times and 0.30 s at ten times. Many relays also have an instantaneous element (ANSI number 50) that trips with no intentional delay above a high current setting, set so it can't see faults beyond the next protection down the line.
Grading: a worked example
Two relays in series must be graded: for any fault the downstream one sees, the upstream one must wait long enough for the downstream breaker to clear it. The gap is the grading margin. It has to cover the downstream breaker's opening time, the relays' errors and overshoot, and a safety margin; for numerical relays and modern breakers it's usually about 0.3 to 0.4 s.
Take a feeder relay with Is = 200 A, standard inverse, TMS 0.1, and an upstream relay with Is = 400 A, standard inverse. The maximum fault current at the feeder relay is 4,000 A. Using a 0.4 s margin:
- Feeder relay: 4,000 ÷ 200 = 20 times setting, so t = 0.1 × 0.14 ÷ (200.02 − 1) = 0.227 s.
- The upstream relay must take at least 0.227 + 0.4 = 0.627 s at 4,000 A, which is 10 times its setting.
- At TMS 1, standard inverse at 10 times setting is 0.14 ÷ (100.02 − 1) = 2.971 s, so TMS = 0.627 ÷ 2.971 = 0.211.
- Rounded up to the next relay step of 0.025: TMS 0.225, which gives 0.67 s at 4,000 A.
Grade at the maximum fault current the downstream relay can see, because that's where the curves come closest together. Then check the upstream relay still trips fast enough for a fault at the far end of its own zone, and that both settings sit above the highest load current and any inrush. The protection coordination simulator lets you grade relays, reclosers and fuses on a real-looking network and then fire faults at it.
Earth fault protection
Most faults on overhead lines involve earth. An earth fault element (51N) measures the residual current: the sum of the three CT currents, which is zero in normal service however the load is shared between the phases (with no earth fault, all the current returns through the phases) and equals the earth fault current when there's a fault. Because load current doesn't show up in it, it can be set well below load current. A sensitive earth fault (SEF) element goes further, picking up a few amps primary with a definite time delay, to catch high-resistance faults such as a conductor lying on dry ground, which may not draw enough current for the normal earth fault element to see.
Other main types
| Number | Function | What it does |
|---|---|---|
| 50 / 51 | Instantaneous / time overcurrent | Trips on high current, instantly or on an IDMT curve |
| 50N / 51N | Earth fault | The same on the residual (earth) current |
| 67 / 67N | Directional overcurrent / earth fault | Only trips for fault current flowing one way, needed on rings and parallel feeders |
| 21 | Distance (impedance) | Measures V ÷ I to work out how far away the fault is, in zones |
| 87 | Differential | Compares current in and out of a zone; trips fast for faults inside it only |
| 79 | Auto-reclose | Recloses the breaker after a trip to clear transient faults |
| 86 | Lockout | Holds the breaker open until someone resets it |
- Distance protection is used on transmission and 132 kV lines. Zone 1 typically covers about 80% of the line and trips instantly; zone 2 reaches past the far end with a short delay; zone 3 is a slower backup. Because it measures impedance, it isn't fooled by changes in the source.
- Differential protection is unit protection: it only protects what's between its CTs, so it needs no time grading and can trip very quickly. It's used on transformers, busbars, generators and important cables, where each end's currents are compared over a pilot cable or fibre link.
- Transformer protection adds restricted earth fault, winding temperature and the Buchholz relay, which catches gas from a slow internal fault in an oil-filled transformer.
Auto-reclosing
Most faults on overhead lines are transient: lightning, a bird, or a branch blown against the wires. Once the breaker opens, the arc goes out and the line is often fine again. An auto-recloser (a pole-mounted recloser or a 79 function in the substation relay) recloses after a short dead time. If the fault is still there it trips again and, after a set number of attempts, locks out. Reclosers work with downstream fuses and sectionalisers, which count the recloser's trips and open during a dead time to isolate a faulty spur, so the rest of the line can be restored.
Going deeper
CT saturation and knee-point voltage
A CT is accurate only while its core isn't saturated. At high fault currents, or with a large burden (relay plus leads), the secondary voltage needed can exceed the CT's knee-point voltage, and the output collapses for part of each cycle. Protection CTs are specified by class (for example 5P20: 5% composite error at 20 times rated current) or, for differential schemes, by knee-point voltage, so they stay accurate up to the highest fault the relay must see.
Fuse and relay grading
Fuses have very steep time-current curves, closest in shape to extremely inverse. When a relay grades with a downstream fuse, the fuse's total clearing time (pre-arcing plus arcing) is used, and margins allow for the fuse's manufacturing tolerance. A recloser's fast trip can be set to beat the fuse ("fuse saving") so a transient fault on a spur doesn't blow the fuse, while its slower trips let the fuse clear a permanent fault.
Reset time
Electromechanical disc relays take time to reset after the current falls, because the disc has to rotate back. Repeated faults close together (for example during reclosing) can make a disc relay trip faster than expected. Numerical relays can emulate this reset so they grade properly with older relays, or reset instantly.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- IEC 60255-151: measuring relays and protection equipment, functional requirements for over/under current protection (curve constants; paid standard)
- Wikipedia: Protective relay, IEC 60255-151 IDMT curve equations and constants (from the Alstom Network Protection and Automation Guide)
- Alstom Grid (now GE Vernova): Network Protection and Automation Guide, chapters on overcurrent, distance and unit protection and grading margins
- IEEE C37.2: standard electrical power system device function numbers (ANSI numbers)