Home / Learn / Electrical installations

UK cable types explained: twin and earth, flex, singles, SWA, FP200 and MICC

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

Cut ends of four UK cables: flat grey twin and earth with brown and blue cores and a bare earth between them, round white three-core flex with brown, blue and green-and-yellow cores, red fire-resistant cable, and black steel wire armoured cable with brown, black and grey cores inside a ring of steel wires
Beginner

Walk into an electrical wholesaler and you'll find dozens of cables. Most installation work uses a handful of types, each with a job it's designed for. This guide explains what they are, how to recognise them and where each one belongs.

Twin and earth (6242Y)fixed wiring, bare CPC3-core and earth (6243Y)two-way lighting strappersFlexible cord (3183Y)appliance leadsFire-resistant (FP200 type)fire alarms, emergency lightsMineral insulated (MICC)copper sheath, powder insideSteel wire armoured (SWA)buried and outdoor runs
Six common UK cables in cross-section (not to scale).

Twin and earth (6242Y)

Flat twin and earth to BS 6004 is the everyday cable for fixed wiring in homes: two insulated cores (brown line, blue neutral) and an uninsulated circuit protective conductor (CPC) between them, all in a grey or white PVC sheath. The bare CPC must be sleeved green-and-yellow wherever the sheath is removed.

The CPC is smaller than the live cores in most sizes, which matters when you check earth fault loop impedance and the adiabatic equation:

Twin and earth conductor and CPC sizes
Live conductorsCPC
1 mm²1 mm²
1.5 mm²1 mm²
2.5 mm²1.5 mm²
4 mm²1.5 mm²
6 mm²2.5 mm²
10 mm²4 mm²
16 mm²6 mm²

Typical uses: 1.0 or 1.5 mm² for lighting, 2.5 mm² for socket rings and radials, 4 or 6 mm² for radial sockets on 32 A, cookers and some showers, 10 mm² for large showers and sub-mains. The right size depends on the circuit, the length and how it's installed: see cable sizing explained.

Three-core and earth (6243Y)

The same construction with three cores: brown, black and grey. Its main use is two-way and intermediate lighting, where the black and grey cores are the strappers between switches; they're line conductors, so sleeve them brown at the terminations. See how to wire a light switch.

Singles and meter tails

  • Singles (single-core insulated, such as 6491X) are run inside conduit or trunking, never on their own without that protection. Use green-and-yellow singles for CPCs and bonding conductors.
  • Meter tails are single-core cables with insulation and a sheath (6181Y), commonly 25 mm² for a home, connecting the meter to the consumer unit.

Flexible cords

Flex has finely stranded conductors so it can bend repeatedly. Round PVC flex (3183Y for three-core) is used for appliance leads and pendants. Where flex will be dragged around, used outdoors or in the cold, use a tougher rubber cord such as H07RN-F. Heat-resistant flex is used for immersion heaters and other hot connections. Cores are brown, blue and green-and-yellow. Flex isn't a substitute for fixed wiring.

Armoured cable (SWA)

Steel wire armoured cable has a layer of steel wires round the cores for mechanical protection, which can also act as the CPC. It's the standard choice for buried supplies to outbuildings, EV chargers and sub-mains. It gets a guide of its own: SWA cable explained.

Fire-resistant cable

Fire alarm and emergency lighting circuits must keep working during a fire, so they use fire-resistant cable, often called by the original brand name FP200. It has insulation that keeps working when the outside burns, an aluminium foil screen with a drain wire, and a red or white sheath. Fire alarm cables are commonly red so they're easy to identify. Fix them with metal clips or ties: BS 7671 requires wiring systems to be supported so they can't collapse early in a fire and tangle people escaping or firefighters, and plastic clips alone soften and fail. Since the 18th edition this applies throughout the installation, not just in escape routes.

Mineral insulated (MICC)

Mineral insulated copper-clad cable has copper conductors packed in magnesium oxide powder inside a seamless copper tube, often with an orange or white plastic outer sheath. It survives fire, high temperatures and mechanical abuse, and lasts a very long time, which is why it's still found in old installations, boiler rooms and fire alarm systems. It needs special pot-and-gland terminations, because the powder absorbs moisture and the insulation resistance falls if the ends aren't sealed.

LSZH sheaths

Ordinary PVC gives off thick black smoke and corrosive hydrogen chloride when it burns. Low smoke, zero halogen (LSZH or LS0H) cables give off much less smoke and no halogen gases, so they're specified in public buildings, escape routes, tunnels and places where people may be trapped. Many common types come in an LSZH version, such as 6242B for twin and earth.

Data and extra-low voltage cables

Network cables (Cat 5e, Cat 6 and Cat 6A), coaxial cables for TV aerials and satellite, and alarm cable all carry signals rather than mains power. Keep them separate from mains cables, or use cables insulated for the highest voltage present, as BS 7671 requires for segregation, and keep data cables away from mains to avoid interference.

Choosing a cable

  1. What's it for: fixed wiring, a flexible lead, a buried supply, or a circuit that must survive fire?
  2. Where is it going: indoors, outdoors, buried, in an escape route, in a hot place?
  3. How much current, how far, and installed how: the size comes from BS 7671 Appendix 4 or a cable sizing calculator.
  4. Does the CPC need to carry a bigger fault current than the cable's CPC can take? If so, choose a cable with a full-size CPC or add a separate one.

The full list of core colours, old and new, is on the cable colours cheat sheet.

Intermediate and advanced

Going deeper

Reading cable codes

UK cable reference numbers come from an old British system. 6242Y is two-core flat with CPC, 6243Y is three-core flat with CPC, and the final letter gives the sheath: Y for PVC, B for LSZH. Harmonised European codes such as H07RN-F describe the construction: H for harmonised, 07 for a rating of 450/750 V, R for rubber insulation, N for a polychloroprene sheath, and F for a flexible conductor.

Thermoplastic versus thermosetting

PVC is thermoplastic: it softens as it heats, so it's limited to a conductor temperature of 70 °C. XLPE and rubber are thermosetting: they don't soften the same way, and XLPE is rated for 90 °C, which is why XLPE cables carry more current for their size. If an XLPE cable runs at 90 °C, check that the terminals of the equipment it connects to are rated for that temperature too.

Aluminium

Some large cables have aluminium conductors to save cost and weight. They need terminals rated for aluminium and careful jointing, because aluminium oxidises and creeps under pressure.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.

  • BS 6004: PVC insulated and sheathed cables for electric power and lighting (twin and earth; paid standard)
  • IEC 60228: Conductors of insulated cables (maximum resistance values, paid standard)
  • BS 7629-1: fire-resistant cables for fire alarm and emergency lighting systems (paid standard)
  • BS 7671:2018+A4:2026 Regulation 521.10.202: wiring systems supported against premature collapse in a fire (IET, paid standard)