Home / Learn / Electrical installations

PAT testing explained: inspection and testing of electrical equipment at work

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A handheld PAT tester with the kettle's plug in its test socket and the earth bond clip on the kettle's metal body, showing PASS for an earth continuity of 0.04 ohms, next to a green PASS label
Beginner

"PAT testing" is the common name for checking that electrical equipment used at work is safe. The proper name is in-service inspection and testing of electrical equipment, and in the UK it usually follows the IET's Code of Practice of that name. This guide explains what the law requires, what the checks involve, and why a green sticker every year isn't always the answer.

What the law says

The Electricity at Work Regulations 1989 apply to work activities. Regulation 4(2) says that, as may be necessary to prevent danger, electrical systems must be maintained so as to prevent danger, so far as is reasonably practicable. Equipment that plugs in is part of that. The regulations don't mention PAT, testing intervals or stickers: they require the equipment to be kept safe. How you do that, and how often, is up to the duty holder, based on risk. The HSE's guidance makes the same point, and says that annual testing isn't needed for everything in a low-risk place like an office.

The regulations generally don't apply in your own home. Landlords have their own duties: in England, social housing landlords must have each appliance they provide checked by a qualified person before each new tenancy and at least every 5 years (since May 2026), and in Scotland, the five-yearly electrical safety inspection covers appliances the landlord provides (see which electrical certificate).

Three levels of checking

User checksevery time it's used, by the person using itFormal visual inspectionat intervals, by someone trained to do itCombined inspection and testless often, by a competent person with a tester
Most faults are found by looking. Testing finds the ones you can't see.
  • User checks. Before using equipment, look at the plug, the lead and the case. Stop using it and report it if there's damage to the lead, tape on the lead, exposed coloured cores where the lead enters the plug or equipment, a cracked plug or case, burn marks, or signs of overheating.
  • Formal visual inspection. A more thorough look by someone trained, including taking the cover off a rewireable plug to check the fuse rating, the cord grip and the connections. No instruments are needed.
  • Combined inspection and test. The formal inspection plus electrical tests with a PAT tester, done by someone competent to interpret the results. Tests find hidden faults, such as a broken earth inside a lead, that can't be seen.

Class I and Class II

Class I: earthedmetal caseE pinfault current flowsto earth, fuse blowsClass II: double insulatedplastic casesymbolno earth: two layersof insulation protect you
The class decides which tests apply.

Class I equipment has exposed metal parts connected to the earth pin, so a fault to the case blows the fuse or trips the protective device. The earth is critical, so it's tested. Class II equipment is double insulated: it has no earth, and is marked with a square inside a square. The 5th edition of the Code accepts that some Class II equipment may need only a visual inspection. Class III equipment is designed to run only on extra-low voltage from a safety source, so it has no mains inside it.

The tests

  • Earth continuity (Class I): the resistance from the earth pin to the exposed metal. It should be very low: the long-standing pass limit is 0.1 Ω plus the resistance of the lead's earth core. For a 2 m lead with 1.0 mm² cores (19.5 mΩ per metre), that's 0.1 + 2 × 0.0195 = about 0.14 Ω. The 5th edition prefers a lower test current than the old high-current bond test.
  • Insulation resistance: between the live conductors joined together and earth, or touchable metal on Class II, at a DC test voltage. A low reading means damaged or damp insulation. The 5th edition revised the test voltages to suit modern electronic equipment, which a high voltage could damage.
  • Protective conductor current or touch current: an alternative to the insulation test for equipment that can't be insulation tested, measured with the equipment running.
  • Polarity for extension leads and IEC leads, and a trip test for portable RCDs.
  • Functional check: does it work properly?

Use the pass limits in the current edition of the Code and your tester's instructions, which depend on the equipment type. A tester that only shows PASS or FAIL is quicker; one that shows readings lets you spot a value that's getting worse over time. See the best PAT testers.

How often?

There's no fixed interval in law. The 4th edition of the Code had a table of suggested intervals; the 5th edition (2020) removed it and asks for frequency to be based on a risk assessment instead. Things that increase the risk, and so call for more frequent checks:

  • the environment: construction sites, workshops, outdoors and kitchens are harsher than offices;
  • how it's used: equipment that's moved, handled or plugged in and out a lot gets damaged more;
  • the type: Class I hand-held tools are higher risk than a Class II desktop computer;
  • who uses it: members of the public or untrained users won't report damage;
  • the history: if inspections keep finding faults, check more often; if they never do, you may be able to check less often.

HSE guidance lists battery-operated equipment under 20 V as needing no checks, though a mains charger for it does. Hired or second-hand equipment should be checked before it's first used.

Records

The law doesn't require labels or certificates, but keeping a record of what was checked, when, and what was found is the easiest way to show the equipment is being maintained and to set sensible intervals. Labels help users see that equipment has been checked.

Intermediate and advanced

Going deeper

Fixed equipment

The 5th edition of the Code covers electrical equipment generally, not just things with a plug. Equipment that's wired in, such as a hand dryer or an air-conditioning unit, can fall between the EICR (which stops at its isolator) and the PAT tester (who sees it as part of the wiring). Make sure your maintenance plan covers it.

Why IT equipment trips RCDs

Computers and other electronic equipment have filters that pass a small current to earth in normal use. Each is harmless, but dozens on one circuit add up and can trip an RCD. Measuring the protective conductor current during testing helps plan how equipment is shared between circuits.

Fake and unsafe products

Counterfeit chargers and appliances bought online often fail basic safety requirements: poor insulation between mains and the low-voltage side, no fuse, or an undersized plug pin. A good inspection includes checking that the product looks genuine and has proper markings.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.