The earth fault loop
Imagine a line conductor touching the metal case of an appliance. Current flows from the supply transformer, through the supply cable, the breaker and the circuit's line conductor (R1) to the fault, then back through the circuit protective conductor (R2), the main earthing terminal and the supply's earth path to the transformer. The total impedance of that loop is the earth fault loop impedance, Zs:
Zs = Ze + (R1 + R2)
Ze is the part outside the installation, set by the supply. UK networks typically quote a maximum of 0.35 Ω for a TN-C-S (PME) supply and 0.8 Ω for TN-S. R1 + R2 depends on the cable size and length.
Why it has to be low enough
While the fault lasts, the metal case is live. The fault current is roughly 230 ÷ Zs, and it must be big enough to make the breaker disconnect quickly, which for most final circuits up to 63 A means within 0.4 seconds. An MCB trips instantly (its magnetic part) once the current reaches a multiple of its rating:
- Type B: 5 times its rating
- Type C: 10 times
- Type D: 20 times
BS 7671 Table 41.3 turns that into a maximum Zs for each breaker: Zs max = (230 × 0.95) ÷ Ia, where Ia is the instant-trip current and 0.95 (Cmin) allows for the supply voltage being at the bottom of its range. For a B32 that gives 1.37 Ω, and for a C32 only 0.68 Ω. Our guide to MCB types B, C and D explains the curves.
Temperature matters
Under fault conditions the cable will be at its working temperature, and copper's resistance rises as it warms. So a designer multiplies the 20 °C conductor resistance by 1.20 to estimate it at 70 °C, the operating temperature of thermoplastic (PVC) cable, before comparing with Table 41.3. When you test a circuit at room temperature, compare your measured value with the lower figure that allows for this (the On-Site Guide and Guidance Note 3 tabulate them, at about 80% of Table 41.3).
When Zs is too high
If the loop impedance is too high, you can shorten the circuit, use a larger cable or a larger cpc, swap a type C for a type B if the load allows it, or rely on an RCD for fault protection. In a TN system an RCD can provide the automatic disconnection instead, because it trips on a few tens of milliamps. TT systems, where Ze is often tens of ohms, depend on RCDs for exactly this reason. Try the RCD lab next.
How this simulation works
R1 + R2 uses the IEC 60228 maximum copper resistances at 20 °C (as in the On-Site Guide) times the length, then times 1.20 for 70 °C. The maximum Zs is calculated as 230 × 0.95 ÷ Ia and rounded to two decimal places, which reproduces the Table 41.3 values. The prospective fault current shown is 230 V ÷ Zs. The model ignores reactance, which only matters for large cables, and doesn't check the cable's current rating or that the cpc can withstand the fault energy (the adiabatic calculator does that). For design work use the max Zs calculator.