Home / Circuit lab / How an RCD trips

RCD residual current simulator

An RCD doesn't measure how much current flows. It measures whether any of it is missing. Add load, leakage and faults, and see exactly when it trips.

Intermediate

230 Vloadfaultearth: back to the supply without passing through the RCDLN

Challenges

  1. Load a 30 mA RCD with 40 A or more and no faults or leakage, and confirm it stays on.
  2. Put a 30 mA RCD in the "may trip" band, between 15 and 30 mA.
  3. Add enough standing leakage to break the 30% guidance on a 30 mA RCD.
  4. Make a fault that a 30 mA RCD must clear within 40 ms.
  5. Find a fault that trips a 30 mA RCD but would leave a 100 mA one in, without question.

Controls

Readings

What an RCD measures

A residual current device passes the line and neutral conductors through the same small magnetic ring. Normally every amp that goes out along the line comes back along the neutral, the two magnetic fields cancel, and nothing happens. If some current finds another way back, through an earth fault or a person, the line and neutral currents no longer match. The difference is the residual current. It magnetises the ring, induces a current in a sensing coil, and that trips the RCD.

That's why a 63 A load doesn't trip a 30 mA RCD at all: line and neutral still match perfectly. Overloads and short circuits between line and neutral are the circuit breaker's job. The RCD only cares about current leaking to earth.

When it must trip

An RCD is labelled with its rated residual operating current, IΔn: commonly 30 mA for additional protection, 100 mA or 300 mA for fault and fire protection on bigger circuits. The product standards (BS EN 61008 and 61009) set a band rather than an exact point:

  • Below 50% of IΔn it must not trip.
  • Between 50% and 100% it may trip.
  • At IΔn it must trip within 300 ms.
  • At twice IΔn, within 150 ms. At five times IΔn, within 40 ms.

These are for ordinary general-type RCDs. Time-delayed S-type RCDs, used upstream for selectivity, are deliberately slower.

Why 30 mA?

A 30 mA RCD gives additional protection against electric shock. It doesn't stop you feeling a shock, but by tripping within tens of milliseconds it greatly reduces the chance of the current disturbing your heart rhythm. BS 7671 requires 30 mA RCD protection for most socket-outlets up to 32 A, for cables buried in walls at less than 50 mm without mechanical protection, and in bathrooms, among other places.

Standing leakage and nuisance tripping

Many appliances leak a little current to earth all the time through the filter capacitors in their power supplies: computers, chargers, LED drivers and washing machines all do. Each one is small, but they add up. BS 7671 (531.3.2) says the protective conductor current in normal use should not exceed 30% of IΔn, which is 9 mA on a 30 mA RCD. Go higher and a small extra leak, or a surge, can push it over the trip point, so it trips "for no reason". The usual fix is to spread circuits across more RCDs or to use RCBOs, one per circuit. Our guide to why an RCD keeps tripping covers how to track the cause down.

How this simulation works

The residual current is the standing leakage plus the fault current, where the fault current is 230 V ÷ the fault resistance, with the fault path's only resistance being the one you set. The trip bands are the BS EN 61008-1 and 61009-1 limits for general (non-delay) RCDs. Leakage is treated as in phase with the supply, so the currents simply add. Real filter leakage is mostly capacitive, and different appliances' leakages don't add up exactly, so real totals are usually a little lower. RCD types (AC, A, F, B) differ in which current waveforms they detect, which this model doesn't cover: see our guide to RCD types. To check test results, use the RCD test calculator.