Home / Reference / EICR code finder

EICR code finder: C1, C2, C3 or no code?

Search what you found during an inspection and see the classification code Electrical Safety First's Best Practice Guide 4 gives it, with the reason. 117 findings, including the ones that shouldn't be coded at all.

  • Reference tool
  • Runs in your browser
  • Checked 28 November 2026
  • Sources

117 findings

  1. C1Danger present· Live parts you can touch

    A breaker is missing from the consumer unit and nothing is fitted in the gap, so live parts can be touched.

    Why: Anyone opening the cover can touch live busbars or terminals. That is danger now, not a possible danger later.

    Compare: C2 A consumer unit without a lockable lid has a blank that isn't secure or durable, so live p…

  2. C1Danger present· Live parts you can touch

    A socket, switch or other accessory is badly damaged and live parts inside can be touched.

    Why: Exposed live parts within reach of anyone using the room.

  3. C1Danger present· Live parts you can touch

    Line or neutral conductors have no insulation, or damaged insulation, and can be touched.

    Why: Bare live metal within reach. A neutral counts too: it can carry current and be at a dangerous voltage.

  4. C1Danger present· Live parts you can touch

    Connections have no enclosure or barrier, or a damaged one, and live parts can be touched.

    Why: The live terminations themselves are accessible.

    Compare: C2 Connections that aren't enclosed, for example at a light fitting

  5. C1Danger present· Live parts you can touch

    Metalwork has become live because of a fault.

    Why: Touching the metal gives a shock now. Isolate first, then record it.

  6. C1Danger present· Live parts you can touch

    Polarity is wrong at the origin of the installation (line and neutral swapped at the intake).

    Why: Every single-pole switch and breaker in the installation is then in the neutral, so circuits that are switched off are still live.

    Compare: C2 Polarity is wrong at a final circuit, a piece of equipment or an accessory (for example a…

  7. C1Danger present· Live parts you can touch

    A ceiling rose, light fitting or junction box has its cover off or broken, and live terminals inside can be touched.

    Why: Live terminals with no enclosure, within reach.

    An everyday case of the guide's own example: Connections have no enclosure or barrier, or a damaged one, and live parts can be touched, so it takes the same code.

  8. C1Danger present· Live parts you can touch

    A socket or switch has come away from the wall and hangs on its cables, with live terminals showing.

    Why: The accessory no longer encloses its live parts.

    An everyday case of the guide's own example: A socket, switch or other accessory is badly damaged and live parts inside can be touched, so it takes the same code.

  9. C1Danger present· Live parts you can touch

    The consumer unit's cover, or part of it, is missing or broken, so busbars or terminals can be touched.

    Why: Live parts inside the board are exposed to anyone using it.

    An everyday case of the guide's own example: Connections have no enclosure or barrier, or a damaged one, and live parts can be touched, so it takes the same code.

  10. C1Danger present· Live parts you can touch

    A live cable has been left with bare ends, for example in an empty back box or where an old cooker or light was removed.

    Why: Bare live conductors that can be touched.

    An everyday case of the guide's own example: Line or neutral conductors have no insulation, or damaged insulation, and can be touched, so it takes the same code.

  11. C1Danger present· Live parts you can touch

    A metal light fitting, radiator, appliance case or switch plate gives a shock or tests live.

    Why: Exposed metalwork has become live because of a fault.

    An everyday case of the guide's own example: Metalwork has become live because of a fault, so it takes the same code.

  12. C2Potentially dangerous· Earthing

    There is no reliable and effective means of earthing for the installation.

    Why: Nothing is dangerous until there is an earth fault. Then exposed metalwork can rise to a dangerous voltage and the protective device may not operate.

  13. C2Potentially dangerous· Earthing

    A metal gas or oil pipe is being used as the means of earthing.

    Why: Gas and oil pipes must never be the earth electrode. A plastic section or a repair can break the path without anyone knowing.

  14. C2Potentially dangerous· Earthing

    A metal public water main is being used as the means of earthing.

    Why: Water mains are often replaced with plastic, which removes the earth with no warning.

  15. C2Potentially dangerous· Earthing

    A circuit has no circuit protective conductor (CPC) but supplies Class I equipment, or switches with metal faceplates.

    Why: The metal parts are meant to be earthed. Without a CPC a fault can leave them live.

    Compare: C3 Circuits with no CPC that only have Class II (all-insulated) equipment, which is unlikely…

  16. C2Potentially dangerous· Earthing

    A socket-outlet has no earth.

    Why: Anything plugged in that relies on its earth (Class I) would have no fault protection.

  17. C2Potentially dangerous· EarthingReg 543.1.1

    The earthing conductor is too small to meet the adiabatic requirement of Regulation 543.1.1.

    Why: It could overheat or fail during an earth fault before the protective device clears it.

  18. C2Potentially dangerous· Earthing

    The earthing conductor is disconnected or broken, at the main earthing terminal or at the supply.

    Why: The installation has no reliable and effective means of earthing.

    An everyday case of the guide's own example: There is no reliable and effective means of earthing for the installation, so it takes the same code.

  19. C2Potentially dangerous· Earthing

    On a TT installation, the earth electrode is missing, broken or corroded through.

    Why: Without a sound electrode there's no reliable and effective means of earthing.

    An everyday case of the guide's own example: There is no reliable and effective means of earthing for the installation, so it takes the same code.

  20. C2Potentially dangerous· Bonding

    There is no effective main protective bonding to extraneous-conductive-parts (such as incoming metal gas or water pipes).

    Why: During a fault, pipework and earthed metalwork can be at different voltages, so someone touching both gets a shock.

  21. C2Potentially dangerous· Bonding

    A main protective bonding conductor is smaller than 6 mm², or shows signs of heat damage.

    Why: Too small to be relied on to carry fault current safely.

    Compare: NC A main bonding conductor is smaller than today's requirement but is at least 6 mm² and sho…

  22. C2Potentially dangerous· Bonding

    A main bonding clamp is loose, corroded, or has come off the pipe.

    Why: The main protective bonding is no longer effective.

    An everyday case of the guide's own example: There is no effective main protective bonding to extraneous-conductive-parts (such as inco…, so it takes the same code.

  23. C2Potentially dangerous· RCDs, AFDDs and SPDsReg 411.3.3

    No RCD additional protection for sockets that could reasonably be used for equipment outdoors.

    Why: A lawnmower or hedge trimmer cut through its lead, with no RCD, is a well-known cause of fatal shocks.

    Compare: C3 No RCD additional protection for a socket that is unlikely to supply equipment outdoors, d…

  24. C2Potentially dangerous· RCDs, AFDDs and SPDs

    On a TT installation, the main RCD (or an old voltage-operated earth-leakage breaker) fails to trip when tested, with an instrument or its test button.

    Why: On TT the RCD usually gives the only fault protection, because the earth electrode resistance is too high for a breaker to trip.

  25. C2Potentially dangerous· RCDs, AFDDs and SPDs

    An RCD giving additional protection to sockets doesn't trip when tested, or trips too slowly.

    Why: Equipment that doesn't work properly in a way that could lead to danger: the sockets have lost their RCD protection.

    An everyday case of the guide's own example: Equipment that doesn't work properly in a way that could lead to danger, so it takes the same code.

  26. C2Potentially dangerous· Fuses, breakers and fault protection

    Polarity is wrong at a final circuit, a piece of equipment or an accessory (for example a switch in the neutral, or line and neutral swapped at a socket).

    Why: Things that are switched off can still be live, and plugged-in equipment can have live parts where they should be dead.

    Compare: C1 Polarity is wrong at the origin of the installation (line and neutral swapped at the intak…

  27. C2Potentially dangerous· Fuses, breakers and fault protection

    A circuit's overcurrent protection doesn't work, for example oversized fuse wire in a rewireable fuse.

    Why: The cable can overheat in an overload or fault without the fuse blowing.

  28. C2Potentially dangerous· Fuses, breakers and fault protection

    Earth fault loop impedance is higher than allowed for the protective device to disconnect in the required time, and there's no RCD on the circuit.

    Why: In an earth fault the device may not trip fast enough, leaving metalwork live for too long. The limit is the one from the BS 7671 version or the maker's data current when it was installed.

  29. C2Potentially dangerous· Fuses, breakers and fault protection

    Separate fuses or breakers in both the line and the neutral (double-pole fusing).

    Why: If only the neutral fuse blows, the circuit stops working but stays live.

  30. C2Potentially dangerous· Fuses, breakers and fault protection

    A protective device or other product is under a safety recall.

    Why: It may not work as it should. Electrical Safety First keeps guidance on product recalls.

  31. C2Potentially dangerous· Fuses, breakers and fault protection

    A TT installation has no RCD at all, so fault protection relies on fuses or breakers that the high earth loop impedance can't operate in time.

    Why: On TT the loop impedance is normally far too high for a fuse or breaker to disconnect in time; with no RCD there's no fault protection.

    An everyday case of the guide's own example: Earth fault loop impedance is higher than allowed for the protective device to disconnect…, so it takes the same code.

  32. C2Potentially dangerous· Fuses, breakers and fault protection

    A fuse or breaker is rated too high for the cable it protects, for example a 32 A breaker on 1.5 mm² cable.

    Why: The cable isn't protected against overload, so the overcurrent protection is ineffective.

    An everyday case of the guide's own example: A circuit's overcurrent protection doesn't work, for example oversized fuse wire in a rewi…, so it takes the same code.

  33. C2Potentially dangerous· Fuses, breakers and fault protection

    A fuse carrier or cartridge has been bridged with a nail, wire, foil or a dead fuse.

    Why: The circuit has no effective overcurrent protection.

    An everyday case of the guide's own example: A circuit's overcurrent protection doesn't work, for example oversized fuse wire in a rewi…, so it takes the same code.

  34. C2Potentially dangerous· Bathrooms and showers

    A socket-outlet (other than SELV or a shaver socket) less than 2.5 m horizontally from the edge of zone 1 in a room with a bath or shower.

    Why: Plugged-in equipment within reach of someone in the bath or shower.

  35. C2Potentially dangerous· Bathrooms and showersReg 701.415.2

    No supplementary bonding in a bathroom where it's needed, because the conditions for leaving it out in Regulation 701.415.2 aren't all met.

    Why: Wet skin lowers body resistance, so differences in voltage between metal parts are more dangerous.

  36. C2Potentially dangerous· Bathrooms and showersReg 414.3 (d)

    A SELV source (such as a transformer for low-voltage lights) installed in zone 0, 1 or 2.

    Why: The mains side of the source is then within the zones.

  37. C2Potentially dangerous· Bathrooms and showersReg 701.512.3

    No RCD additional protection for a circuit supplying a socket in a room with a bath or shower.

    Why: Required by Regulation 701.512.3.

    Compare: C3 No RCD additional protection for bathroom circuits other than sockets (lights, fan, shower…

  38. C2Potentially dangerous· Bathrooms and showersReg 701.512.2

    A light fitting inside a shower enclosure or above the bath, in zone 1, isn't rated at least IPX4.

    Why: Its IP rating is too low for where it is, so it's potentially dangerous.

    An everyday case of the guide's own example: Equipment with too low an IP rating for where it is, so that it's potentially dangerous, so it takes the same code.

  39. C2Potentially dangerous· Wiring and connections

    Conductors are badly inserted or in the wrong place in a terminal.

    Why: A poor connection can overheat or come loose.

  40. C2Potentially dangerous· Wiring and connections

    A terminal screw is clamped on the insulation, not the copper.

    Why: No reliable connection: it will arc and overheat.

  41. C2Potentially dangerous· Wiring and connections

    The type, number or size of conductors doesn't suit the terminal.

    Why: Overfilled or mismatched terminals can't make a sound connection.

  42. C2Potentially dangerous· Wiring and connections

    A loose connection showing signs of overheating.

    Why: Heat damage is evidence the fire risk is real.

  43. C2Potentially dangerous· Wiring and connections

    A borrowed neutral, where one circuit's neutral also serves another separately protected circuit (often upstairs and downstairs lights).

    Why: Isolating one circuit can leave the other's neutral live, and RCDs trip for no clear reason.

  44. C2Potentially dangerous· Wiring and connections

    A ring final circuit has a broken (discontinuous) conductor.

    Why: Each leg is then fed from one end only and can carry more current than the cable is rated for.

  45. C2Potentially dangerous· Wiring and connections

    A ring final circuit is cross-connected with another circuit (live or protective conductors).

    Why: Isolating one circuit doesn't make it dead.

  46. C2Potentially dangerous· Wiring and connections

    Insulation has deteriorated so badly that it breaks away from the conductors.

    Why: Bare conductors are only a knock away. Common with old rubber cable.

  47. C2Potentially dangerous· Wiring and connections

    Insulation resistance below 1 MΩ between live conductors connected together and earth.

    Why: A sign of damaged or deteriorated insulation, with leakage that could lead to shock or fire.

  48. C2Potentially dangerous· Wiring and connections

    A cable's sheath stops short of the accessory enclosure, and the bare-insulated cores can be touched or could rub on metal.

    Why: The single layer of core insulation is the only protection.

    Compare: C3 A cable's sheath stops short of the accessory enclosure, but the cores can't be touched an…

  49. C2Potentially dangerous· Wiring and connections

    Connections that aren't enclosed, for example at a light fitting.

    Why: A fault at the joint can start a fire. (If live parts can actually be touched, see C1.)

    Compare: C1 Connections have no enclosure or barrier, or a damaged one, and live parts can be touched

  50. C2Potentially dangerous· Wiring and connections

    Wiring not supported against early collapse in a fire, where falling cables would hinder escape or firefighting (for example a communal escape route).

    Why: Collapsed cables can trap people and firefighters.

  51. C2Potentially dangerous· Wiring and connections

    A joint made with insulating tape or a loose connector block, not inside an enclosure, under a floor or in a ceiling void.

    Why: Unenclosed connections can contribute to a fire.

    An everyday case of the guide's own example: Connections that aren't enclosed, for example at a light fitting, so it takes the same code.

  52. C2Potentially dangerous· Wiring and connections

    A terminal in the consumer unit, such as on a breaker or the neutral bar, is discoloured or melted.

    Why: A poor connection that is overheating.

    An everyday case of the guide's own example: A loose connection showing signs of overheating, so it takes the same code.

  53. C2Potentially dangerous· Consumer units and accessories

    A consumer unit without a lockable lid has a blank that isn't secure or durable, so live parts could be reached.

    Why: Anyone can open the lid and the blank could come out.

    Compare: C3 A consumer unit with a lockable lid has a blank that isn't secure or durable

  54. C2Potentially dangerous· Consumer units and accessories

    Breakers of another make in a consumer unit, not verified by the makers, AND one of these: heat damage, the enclosure modified to fit them, not securely fitted or poor connections, operating wrongly, or toggles working the opposite way to the others.

    Why: Unverified mixes with any of those signs are potentially dangerous. BEAMA publishes guidance on this.

    Compare: C3 Breakers of another make, not verified by the makers, but with none of those warning signs…

  55. C2Potentially dangerous· Consumer units and accessories

    Equipment that doesn't work properly in a way that could lead to danger.

    Why: For example a switch that doesn't break the circuit when off.

  56. C2Potentially dangerous· Consumer units and accessories

    Equipment with too low an IP rating for where it is, so that it's potentially dangerous.

    Why: Water or dust can get to live parts.

  57. C2Potentially dangerous· Consumer units and accessories

    An immersion heater without the built-in 98 °C safety cut-out required by BS EN 60335-2-73, in a system with a plastic cold-water tank.

    Why: If the thermostat fails, boiling water can melt the plastic tank.

  58. C2Potentially dangerous· Consumer units and accessories

    An indoor-type socket, switch or fitting is installed outside where it's exposed to rain.

    Why: Its IP rating is too low for the location, so it's potentially dangerous.

    An everyday case of the guide's own example: Equipment with too low an IP rating for where it is, so that it's potentially dangerous, so it takes the same code.

  59. C2Potentially dangerous· Fire and heat

    Signs of excessive heat, such as charring from electrical equipment damaging the installation or what's around it.

    Why: Clear evidence of a fire risk.

  60. C2Potentially dangerous· Fire and heat

    A fire risk from badly installed equipment, such as a breached fire barrier (usually in buildings other than a single home).

    Why: Fire and smoke can spread past the barrier. ESF's Best Practice Guide 5 has more.

  61. C2Potentially dangerous· Fire and heat

    Lamps above the light fitting's maximum wattage, or too close to something that can burn.

    Why: A fire risk. ESF's Best Practice Guide 5 has more.

  62. C2Potentially dangerous· Fire and heat

    A socket, plug top, switch, cooker switch or shower switch shows scorching or melting.

    Why: Evidence of excessive heat damaging the installation.

    An everyday case of the guide's own example: Signs of excessive heat, such as charring from electrical equipment damaging the installat…, so it takes the same code.

  63. C2Potentially dangerous· Fire and heat

    Downlights buried in loft insulation or touching timber, where the fitting isn't made for it, especially with signs of heat.

    Why: A fire risk from lamps too close to combustible material.

    An everyday case of the guide's own example: Lamps above the light fitting's maximum wattage, or too close to something that can burn, so it takes the same code.

  64. C2Potentially dangerous· Meter cupboards and the supply

    Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a key or tool, BUT the door or lock isn't secure, the hinges or fixings are faulty, the insulation is damaged, or it could foreseeably get damaged.

    Why: The cupboard isn't reliably keeping people away from it.

    Compare: C3 Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a ke…

  65. C3Improvement recommended· Earthing

    Circuits with no CPC that only have Class II (all-insulated) equipment, which is unlikely to be swapped for Class I.

    Why: Improvement recommended. If it supplies metal fittings or switches, see C2.

    Compare: C2 A circuit has no circuit protective conductor (CPC) but supplies Class I equipment, or swi…

  66. C3Improvement recommended· Bonding

    A main bonding connection to gas, water or another installation pipe is hidden where it can't be inspected, tested or maintained.

    Why: Improvement only, provided continuity testing shows the bond is adequate.

  67. C3Improvement recommended· Bonding

    A main bonding connection is made on a branch pipe where continuity back to the main pipe isn't assured.

    Why: Bonding should be made where the service enters, so the bond can't be lost if the branch is changed.

  68. C3Improvement recommended· RCDs, AFDDs and SPDsReg 411.3.3

    No RCD additional protection for a socket that is unlikely to supply equipment outdoors, doesn't serve a bathroom, and isn't otherwise considered dangerous.

    Why: Improvement recommended. The inspector judges how the socket is likely to be used.

    Compare: C2 No RCD additional protection for sockets that could reasonably be used for equipment outdo…

  69. C3Improvement recommended· RCDs, AFDDs and SPDs

    A Type AC RCD is fitted where a Type A is required.

    Why: Type AC may not respond properly to the DC components from modern electronic loads. Improvement recommended.

  70. C3Improvement recommended· RCDs, AFDDs and SPDsReg 411.3.4

    No RCD additional protection for lighting circuits in a home.

    Why: Required for new work, but its absence in an existing installation is an improvement, not a danger.

  71. C3Improvement recommended· RCDs, AFDDs and SPDs

    No RCD for cables buried less than 50 mm deep in a wall or partition, where the cable has no earthed metal covering, earthed metal enclosure or protection against nails.

    Why: Improvement recommended: an RCD reduces the risk from someone drilling or nailing into the cable.

  72. C3Improvement recommended· RCDs, AFDDs and SPDs

    An EV charge point is supplied through a Type A or Type F RCD and has no RDC-DD (DC fault detection).

    Why: Smooth DC fault current from the charger can stop an A or F type RCD working. Improvement recommended.

  73. C3Improvement recommended· RCDs, AFDDs and SPDsReg 722.411.4.1

    An EV charge point that can charge a car outdoors is connected to a PME earth and doesn't meet the requirements of Regulation 722.411.4.1.

    Why: A broken PEN conductor could make the car's body live. Improvement recommended.

  74. C3Improvement recommended· RCDs, AFDDs and SPDsReg 421.1.7

    No AFDD in a high-rise residential building, house in multiple occupation, purpose-built student accommodation or care home.

    Why: These are the premises where BS 7671 now requires AFDDs on socket circuits. Improvement recommended.

    Compare: Obs No AFDD in any other kind of premises, such as an ordinary house

  75. C3Improvement recommended· RCDs, AFDDs and SPDsReg 443.4.1

    No surge protective device (SPD) where Regulation 443.4.1 (a) or (c) requires one.

    Why: Improvement recommended.

  76. C3Improvement recommended· RCDs, AFDDs and SPDsReg 531.3.3

    A Type AC RCD protects socket-outlet circuits, which can supply equipment with DC leakage.

    Why: A Type A is required there, because Type AC is only for fixed equipment known to have no DC components.

    An everyday case of the guide's own example: A Type AC RCD is fitted where a Type A is required, so it takes the same code.

  77. C3Improvement recommended· Fuses, breakers and fault protection

    The installation relies on a voltage-operated earth-leakage circuit-breaker for fault protection (and it works when tested).

    Why: An outdated device. Improvement recommended. If it fails its test on TT, see the C2 entry.

    Compare: C2 On a TT installation, the main RCD (or an old voltage-operated earth-leakage breaker) fail…

  78. C3Improvement recommended· Bathrooms and showers

    No RCD additional protection for bathroom circuits other than sockets (lights, fan, shower), where satisfactory supplementary bonding is present.

    Why: Improvement recommended. Without the supplementary bonding it could be more serious.

    Compare: C2 No RCD additional protection for a circuit supplying a socket in a room with a bath or sho…

  79. C3Improvement recommended· Wiring and connections

    A cable's sheath stops short of the accessory enclosure, but the cores can't be touched and won't contact metal.

    Why: Improvement recommended.

    Compare: C2 A cable's sheath stops short of the accessory enclosure, and the bare-insulated cores can…

  80. C3Improvement recommended· Wiring and connections

    Cables, including meter tails, not supported well enough to keep strain off the terminations.

    Why: Improvement recommended.

  81. C3Improvement recommended· Wiring and connections

    Unsheathed flex used for a pendant light.

    Why: Improvement recommended.

  82. C3Improvement recommended· Wiring and connections

    The green and yellow core of a multicore cable has been oversleeved and used as a live conductor.

    Why: Green and yellow should only ever be a protective conductor. Improvement recommended.

  83. C3Improvement recommended· Wiring and connections

    PVC/PVC cable run outside in sunlight and weather, with no sign yet of deterioration.

    Why: Improvement recommended: UV breaks it down over time.

  84. C3Improvement recommended· Wiring and connections

    An assembly fed from more than one source (such as solar or a battery) has an inadequate current rating, with no sign of heat damage.

    Why: Improvement recommended.

  85. C3Improvement recommended· Consumer units and accessories

    A consumer unit with a lockable lid has a blank that isn't secure or durable.

    Why: The lock keeps ordinary people out, so improvement recommended.

    Compare: C2 A consumer unit without a lockable lid has a blank that isn't secure or durable, so live p…

  86. C3Improvement recommended· Consumer units and accessories

    Breakers of another make, not verified by the makers, but with none of those warning signs: no heat damage, no modification, securely fitted, good connections, working properly, toggles the same way.

    Why: Improvement recommended.

    Compare: C2 Breakers of another make in a consumer unit, not verified by the makers, AND one of these:…

  87. C3Improvement recommended· Consumer units and accessories

    A socket mounted where the socket, plug or flex is likely to get damaged.

    Why: Improvement recommended.

  88. C3Improvement recommended· Consumer units and accessories

    A socket placed where heat, water or knocks are likely to damage it, the plug or the flex, such as right behind a hob or at floor level where it's kicked.

    Why: Improvement recommended: the position is likely to lead to damage.

    An everyday case of the guide's own example: A socket mounted where the socket, plug or flex is likely to get damaged, so it takes the same code.

  89. C3Improvement recommended· Fire and heat

    A plastic (combustible) consumer unit, not in a non-combustible enclosure, under a wooden staircase or on the only escape route.

    Why: Improvement recommended.

    Compare: NC A plastic consumer unit, not in a non-combustible enclosure, somewhere other than under a…

  90. C3Improvement recommended· Meter cupboards and the supply

    Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a key or tool, and the door, lock, hinges and insulation are all sound with no foreseeable risk of damage.

    Why: Improvement recommended.

    Compare: C2 Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a ke…

  91. C3Improvement recommended· Labels and notices

    No warning notice for an alternative or second source of supply, such as solar PV, a battery or a generator.

    Why: Someone isolating the main supply may think the installation is dead.

  92. C3Improvement recommended· Labels and noticesReg 514.13.1

    No 'Safety electrical connection, do not remove' label where one is required.

    Why: Improvement recommended.

  93. C3Improvement recommended· Labels and notices

    Circuits protected by each breaker or fuse in the consumer unit aren't identified.

    Why: Improvement recommended: it matters when someone needs to isolate quickly.

  94. ObsObservation, not coded· RCDs, AFDDs and SPDs

    No AFDD in any other kind of premises, such as an ordinary house.

    Why: Worth noting, but not coded.

    Compare: C3 No AFDD in a high-rise residential building, house in multiple occupation, purpose-built s…

  95. ObsObservation, not coded· Consumer units and accessories

    The consumer unit can be reached for use, testing and maintenance, but it's mounted high up.

    Why: Worth noting, not coded.

  96. ObsObservation, not coded· Fire and heat

    Things that burn stored close to the intake equipment (consumer unit, meter, service head).

    Why: Worth noting, not coded.

  97. ObsObservation, not coded· Fire and heat

    No fire detection and alarm system (smoke, heat or carbon monoxide alarms).

    Why: Worth noting, not coded. Separate laws may require alarms, especially in rented homes.

  98. ObsObservation, not coded· Fire and heat

    No emergency lighting where it would normally be needed, such as a communal area of a block of flats.

    Why: Worth noting, not coded.

  99. NCNon-compliance only, not recorded· Earthing

    No reliable earth connection to a sunk metal back box behind an insulated accessory (no earthing tail and no fixed lug).

    Why: Not recorded on an EICR.

  100. NCNon-compliance only, not recorded· Bonding

    A main bonding conductor is smaller than today's requirement but is at least 6 mm² and shows no heat damage.

    Why: A non-compliance with the current edition only. The guide says it doesn't need recording on an EICR.

    Compare: C2 A main protective bonding conductor is smaller than 6 mm², or shows signs of heat damage

  101. NCNon-compliance only, not recorded· Fuses, breakers and fault protection

    Meter tails longer than 3 m with no overcurrent protection at the consumer end (and maximum Zs is satisfactory).

    Why: A non-compliance only. Not recorded on an EICR.

  102. NCNon-compliance only, not recorded· Wiring and connections

    Cable core colours from an earlier edition of BS 7671 (red and black).

    Why: Non-compliance with today's edition only. Not recorded on an EICR.

  103. NCNon-compliance only, not recorded· Wiring and connections

    Switch lines not marked as line conductors (a blue core not sleeved brown at the switch or light).

    Why: Not recorded on an EICR.

  104. NCNon-compliance only, not recorded· Wiring and connections

    The bare CPC in twin and earth not sleeved green and yellow.

    Why: Not recorded on an EICR.

  105. NCNon-compliance only, not recorded· Wiring and connections

    Conductors in the consumer unit not arranged or marked so each circuit's conductors can be identified.

    Why: Not recorded on an EICR.

  106. NCNon-compliance only, not recorded· Wiring and connections

    A lighting circuit's CPC not terminated (or wrongly terminated) at a Class II item, such as a plastic switch box or fitting.

    Why: Not recorded on an EICR.

  107. NCNon-compliance only, not recorded· Wiring and connections

    Too few circuits to keep inconvenience low during faults or testing, for example one RCD covering the whole installation.

    Why: Not recorded on an EICR.

  108. NCNon-compliance only, not recorded· Fire and heat

    A plastic consumer unit, not in a non-combustible enclosure, somewhere other than under a wooden staircase or on the only escape route.

    Why: Not recorded on an EICR.

    Compare: C3 A plastic (combustible) consumer unit, not in a non-combustible enclosure, under a wooden…

  109. MythMyth, not a fault· Bonding

    No earthing or bonding to a metal sink or bath.

    Why: Not a fault, unless the sink or bath is an extraneous-conductive-part in its own right (it introduces a potential, usually Earth, from outside). Most are not.

  110. MythMyth, not a fault· Bonding

    No bonding connections to the boiler pipework.

    Why: Not a fault, unless that pipework is itself an extraneous-conductive-part.

  111. MythMyth, not a fault· Fuses, breakers and fault protection

    Circuit-breakers made to BS 3871.

    Why: An old standard isn't a fault in itself. Don't code it.

  112. MythMyth, not a fault· Fuses, breakers and fault protection

    Rewireable fuses, where they still give adequate protection.

    Why: Not a fault in itself. Don't code it (wrong fuse wire is a different matter, see C2).

    Compare: C2 A circuit's overcurrent protection doesn't work, for example oversized fuse wire in a rewi…

  113. MythMyth, not a fault· Bathrooms and showers

    A shaver supply unit to BS EN 61558-2-5 in zone 2, placed where direct spray from the shower is unlikely.

    Why: Allowed. Don't code it.

  114. MythMyth, not a fault· Consumer units and accessories

    No barriers inside a consumer unit, where the cover can only be removed with a key or tool.

    Why: Not a fault. Don't code it.

  115. MythMyth, not a fault· Consumer units and accessories

    Unswitched sockets or fused connection units.

    Why: Not a fault. Don't code it.

  116. MythMyth, not a fault· Other things that come up

    Anything not directly related to electrical safety, such as a socket in an awkward place or a wish for more sockets.

    Why: An EICR is about whether the installation is safe to keep using. Don't code it.

  117. DNONetwork operator's equipment· Meter cupboards and the supply

    A problem with the network operator's or supplier's equipment (service head, cut-out, meter, their earth).

    Why: Inspect it visually only and mark it on the report, but it doesn't decide the outcome unless live parts can be touched. Tell the client to report anything dangerous on 105.

Will the report be satisfactory?

Enter how many observations of each code are on the report (BS 7671:2018+A4:2026 rules).

SatisfactoryNo C1 or C2 observations, so the overall condition can be reported as satisfactory.

What the codes mean

C1

Danger present. Risk of injury now. Immediate action: the inspector should make it safe there and then (with the client's agreement), and tell the client straight away and in writing.

C2

Potentially dangerous. Not dangerous right now, but would become a danger if a fault or other foreseeable event happened. Urgent action.

C3

Improvement recommended. Not a danger, but fixing it would make the installation safer.

FI

Further investigation is advised. A possible issue the inspector couldn't pin down within the agreed limits. Should be rare in a home: the guide gives no domestic FI examples.

Each observation gets one code only, the most serious that applies. The guide also names three things that get no code at all: an Obs is worth noting but isn't a non-compliance; an NC breaks today's edition of BS 7671 but isn't dangerous and needn't be on the report; and a Myth isn't a non-compliance at all. An installation built to an older edition isn't unsafe just because it doesn't meet the current one.

How the codes decide the outcome

  • One or more C1 or C2: the overall condition must be reported as unsatisfactory.
  • Only C3s, or C3s and FIs: the report can be satisfactory. Under BS 7671:2018+A4:2026 an FI no longer makes a report unsatisfactory on its own (older reports done to the earlier version followed the old rule).
  • The recommended date for the next inspection assumes every C1 is fixed immediately and every C2 urgently.
  • Problems with the network operator's equipment (service head, cut-out, meter, their earth) are marked on the report but don't decide the outcome unless live parts can be touched. The client should report anything dangerous to the network operator on 105.

For a rented home in England, the landlord must have any remedial work or further investigation done within 28 days, or sooner if the report says so. Our guide EICR codes explained covers the landlord rules and Amendment 4 in more detail.

Same finding, different code

These pairs catch people out. The difference is usually whether live parts can be reached, how the circuit is likely to be used, or what else is present.

FindingCodeCompared withCode
A breaker is missing from the consumer unit and nothing is fitted in the gap, so live parts can be touched.C1A consumer unit without a lockable lid has a blank that isn't secure or durable, so live parts could be reached.C2
Connections have no enclosure or barrier, or a damaged one, and live parts can be touched.C1Connections that aren't enclosed, for example at a light fitting.C2
Polarity is wrong at the origin of the installation (line and neutral swapped at the intake).C1Polarity is wrong at a final circuit, a piece of equipment or an accessory (for example a switch in the neutral, or line and neutral swapped at a socket).C2
A circuit has no circuit protective conductor (CPC) but supplies Class I equipment, or switches with metal faceplates.C2Circuits with no CPC that only have Class II (all-insulated) equipment, which is unlikely to be swapped for Class I.C3
A main protective bonding conductor is smaller than 6 mm², or shows signs of heat damage.C2A main bonding conductor is smaller than today's requirement but is at least 6 mm² and shows no heat damage.NC
No RCD additional protection for sockets that could reasonably be used for equipment outdoors.C2No RCD additional protection for a socket that is unlikely to supply equipment outdoors, doesn't serve a bathroom, and isn't otherwise considered dangerous.C3
No AFDD in a high-rise residential building, house in multiple occupation, purpose-built student accommodation or care home.C3No AFDD in any other kind of premises, such as an ordinary house.Obs
No RCD additional protection for a circuit supplying a socket in a room with a bath or shower.C2No RCD additional protection for bathroom circuits other than sockets (lights, fan, shower), where satisfactory supplementary bonding is present.C3
A cable's sheath stops short of the accessory enclosure, and the bare-insulated cores can be touched or could rub on metal.C2A cable's sheath stops short of the accessory enclosure, but the cores can't be touched and won't contact metal.C3
A consumer unit without a lockable lid has a blank that isn't secure or durable, so live parts could be reached.C2A consumer unit with a lockable lid has a blank that isn't secure or durable.C3
Breakers of another make in a consumer unit, not verified by the makers, AND one of these: heat damage, the enclosure modified to fit them, not securely fitted or poor connections, operating wrongly, or toggles working the opposite way to the others.C2Breakers of another make, not verified by the makers, but with none of those warning signs: no heat damage, no modification, securely fitted, good connections, working properly, toggles the same way.C3
A plastic (combustible) consumer unit, not in a non-combustible enclosure, under a wooden staircase or on the only escape route.C3A plastic consumer unit, not in a non-combustible enclosure, somewhere other than under a wooden staircase or on the only escape route.NC
Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a key or tool, BUT the door or lock isn't secure, the hinges or fixings are faulty, the insulation is damaged, or it could foreseeably get damaged.C2Basic insulation of a conductor in the meter cupboard is exposed, reachable only with a key or tool, and the door, lock, hinges and insulation are all sound with no foreseeable risk of damage.C3

Where these codes come from

97 of the findings are every example in Electrical Safety First's Best Practice Guide 4 (Issue 7.4, August 2026, written to BS 7671:2018+A4:2026) lists, each with the guide's own code. The other 20 are everyday versions of those examples (a taped joint in a ceiling void is a case of the guide's "unenclosed connections"), and each one links to the example it follows and takes the same code. The guide is produced with the IET, NICEIC, NAPIT, ECA, SELECT, BEAMA and others, and it's strongly recommended that inspectors follow it: an inspector who departs from it has to be able to justify why. The descriptions here are our own plain-English summaries, so check the guide itself for the exact wording.

The examples aren't exhaustive, and coding is still a judgement made by the competent person who signs the report, based on the actual risk in that installation. Nobody ordering the work should be able to push the code up or down. Practise coding a whole house in the EICR report-writing simulator, which marks every code against the same guide.

Sources

Every code on this page was checked against Best Practice Guide 4, Issue 7.4, on 28 November 2026.