Working smoke alarms give people the minutes they need to get out of a house fire. The rules about them differ across the UK, and fitting them well matters as much as fitting them at all. This guide covers the types, where they go, how they're powered and linked, and what the law requires.
Types of alarm
| Type | How it works | Best for |
|---|---|---|
| Optical (photoelectric) smoke | Detects smoke particles scattering a light beam inside the chamber | Slow, smouldering fires such as furniture; hallways and landings. Less prone to false alarms from cooking than ionisation types |
| Ionisation smoke | Detects small particles that interrupt a tiny current in an ionised chamber | Fast, flaming fires; now much less common and prone to false alarms near kitchens |
| Multi-sensor | Combines optical and heat sensing to respond to more types of fire and reject false alarms | Living rooms and circulation spaces |
| Heat | Sounds when the temperature reaches a fixed level or rises quickly; doesn't react to smoke | Kitchens, where cooking fumes would set off a smoke alarm |
| Carbon monoxide (CO) | An electrochemical sensor detects CO gas, which has no smell | Rooms with a boiler, gas fire, wood burner or other fuel-burning appliance (to BS EN 50291) |
Where to fit them
- S: smoke alarm on the ceiling
- H: heat alarm in the kitchen
- CO: carbon monoxide alarm in the room with the boiler
- Dashed purple line: smoke and heat alarms interlinked, so one sounds them all
- Fit smoke and heat alarms on the ceiling, near the middle of the room or hall, because smoke and hot gases rise and spread across the ceiling first.
- BS 5839-6 recommends keeping them at least 300 mm from walls and light fittings, where the air doesn't flow well.
- Put one in the hallway and on every landing, so the escape route is covered, and one in the main living room.
- Don't put smoke alarms in kitchens, bathrooms or garages, or right next to a cooker, shower or heater, where steam and fumes cause false alarms. Use a heat alarm in a kitchen.
- Fit CO alarms in the same room as the appliance, following the manufacturer's instructions: typically 1 to 3 m from it, either on the ceiling or high on a wall.
Grades and categories (BS 5839-6)
BS 5839-6 is the British Standard for fire detection in homes. It describes a system by its grade (how it's powered and how reliable it is) and its category (how much of the home it covers).
| Code | Meaning |
|---|---|
| Grade D1 | Mains-powered alarms with a sealed, built-in standby battery that lasts the life of the alarm |
| Grade D2 | Mains-powered alarms with a user-replaceable standby battery |
| Grade F1 / F2 | Battery-only alarms: F1 with a sealed long-life battery, F2 with a replaceable one |
| Category LD3 | Alarms in the escape route: hallways and landings |
| Category LD2 | LD3 plus the rooms where a fire is most likely to start, such as the living room and kitchen |
| Category LD1 | LD2 plus every room where a fire could start, except bathrooms and the like |
In England, Approved Document B asks for at least a Grade D2, Category LD3 system in new homes, mains-powered with a standby supply and interlinked. Many designers go further, to LD2.
Mains-powered and interlinked
Interlinked means that when one alarm detects fire, they all sound, so someone asleep upstairs hears a fire that starts in the kitchen. Links can be wired (an extra core between alarms) or radio. Mains alarms are supplied from either their own dedicated circuit or a regularly used lighting circuit, as BS 5839-6 allows; a lighting circuit has the advantage that a fault there is noticed quickly. Mains alarms still have a standby battery so they work in a power cut.
Testing and replacing
- Press the test button monthly. It checks the sounder and battery, and on interlinked systems that the others sound too.
- Vacuum or dust the vents now and then, following the maker's instructions.
- Replace alarms by the date on the label, usually 10 years after manufacture; the sensors degrade with age. CO alarms have a shorter or similar life: check the label.
- If an alarm chirps, it's usually a low battery or the end of its life, not a fault to ignore.
What the law requires
| Nation | Who it applies to | What's required |
|---|---|---|
| England | Landlords of rented homes | A smoke alarm on each storey with a room used as living accommodation (a bathroom or toilet counts), and a CO alarm in any room with a fixed combustion appliance, other than a gas cooker. Check they work on the first day of each new tenancy, and repair or replace them once told they're faulty (The Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended in 2022) |
| Wales | Landlords under the Renting Homes (Wales) Act | A smoke alarm on each storey that is in working order, connected to the mains and interlinked with every other mains smoke alarm; a CO alarm in each room with a gas, oil-fired or solid-fuel appliance (The Renting Homes (Fitness for Human Habitation) (Wales) Regulations 2022) |
| Scotland | Every home, owned or rented, since 1 February 2022 | Smoke alarms in the living room (the room you spend most of the day in) and every hallway and landing, a heat alarm in every kitchen, all ceiling-mounted and interlinked; a CO alarm where there's a fixed combustion appliance, such as a boiler or wood burner. Alarms can be mains-wired or sealed, tamper-proof long-life lithium battery units (the tolerable standard, and Scottish Government guidance) |
New homes, and major works such as extensions and loft conversions, also have to meet the building regulations in each nation, which ask for mains-powered, interlinked systems. Northern Ireland has its own rules.
Going deeper
Why heat alarms in kitchens
Cooking makes smoke and steam, so a smoke alarm in a kitchen goes off often. People then take its battery out or cover it, which is worse than no alarm. A heat alarm only responds to a high or quickly rising temperature, so it ignores toast but still warns of a pan fire, and because it's interlinked it wakes the whole house.
Coverage distances
BS 5839-6 sets how far any point in a room or hall can be from the nearest detector: in general 7.5 m for a smoke detector and 5.3 m for a heat detector. That means a long hallway or a big open-plan room may need more than one.
RCDs and smoke alarm circuits
Because mains alarms have a standby battery, an RCD trip doesn't stop them working, but the circuit arrangement should mean a trip is noticed and dealt with. If the alarms share a circuit with lighting, a trip leaves the lights off too, which people notice and fix. Follow BS 5839-6 and BS 7671 together when designing the supply.
Sources
The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.
- BS 5839-6:2019+A1:2020 Fire detection and fire alarm systems for buildings, Part 6: domestic premises (paid standard)
- BS EN 50291: Gas detectors, electrical apparatus for the detection of carbon monoxide in domestic premises (paid standard)
- The Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4 (as amended 2022)
- The Renting Homes (Fitness for Human Habitation) (Wales) Regulations 2022, regulations 5 and 6
- The Housing (Scotland) Act 1987 (Tolerable Standard) (Extension of Criteria) Order 2019
- Scottish Government: Fire and smoke alarms in Scottish homes, where and what to buy
- Approved Document B (fire safety), Volume 1: Dwellings, section 1 (fire detection and alarm systems)