Home / Learn / Electrical installations

Smoke, heat and CO alarms in UK homes: types, where to fit them and the law

New to this? Read from the top. Already know the basics? Jump to Going deeper for intermediate and advanced detail.

A ceiling smoke alarm and a heat alarm, interlinked so one sounding sets off both, and a wall-mounted carbon monoxide alarm reading 0 ppm. Test monthly and replace by the date on the label
Beginner

Working smoke alarms give people the minutes they need to get out of a house fire. The rules about them differ across the UK, and fitting them well matters as much as fitting them at all. This guide covers the types, where they go, how they're powered and linked, and what the law requires.

Types of alarm

Common types of domestic fire and CO alarm
TypeHow it worksBest for
Optical (photoelectric) smokeDetects smoke particles scattering a light beam inside the chamberSlow, smouldering fires such as furniture; hallways and landings. Less prone to false alarms from cooking than ionisation types
Ionisation smokeDetects small particles that interrupt a tiny current in an ionised chamberFast, flaming fires; now much less common and prone to false alarms near kitchens
Multi-sensorCombines optical and heat sensing to respond to more types of fire and reject false alarmsLiving rooms and circulation spaces
HeatSounds when the temperature reaches a fixed level or rises quickly; doesn't react to smokeKitchens, where cooking fumes would set off a smoke alarm
Carbon monoxide (CO)An electrochemical sensor detects CO gas, which has no smellRooms with a boiler, gas fire, wood burner or other fuel-burning appliance (to BS EN 50291)

Where to fit them

bedroomlandingbedroomliving roomhallwaykitchenSSSHboilerCO
A typical layout meeting the Scottish standard: smoke alarms in the living room, hallway and landing, a heat alarm in the kitchen, all interlinked, and a CO alarm by the boiler.
  • S: smoke alarm on the ceiling
  • H: heat alarm in the kitchen
  • CO: carbon monoxide alarm in the room with the boiler
  • Dashed purple line: smoke and heat alarms interlinked, so one sounds them all
  • Fit smoke and heat alarms on the ceiling, near the middle of the room or hall, because smoke and hot gases rise and spread across the ceiling first.
  • BS 5839-6 recommends keeping them at least 300 mm from walls and light fittings, where the air doesn't flow well.
  • Put one in the hallway and on every landing, so the escape route is covered, and one in the main living room.
  • Don't put smoke alarms in kitchens, bathrooms or garages, or right next to a cooker, shower or heater, where steam and fumes cause false alarms. Use a heat alarm in a kitchen.
  • Fit CO alarms in the same room as the appliance, following the manufacturer's instructions: typically 1 to 3 m from it, either on the ceiling or high on a wall.

Grades and categories (BS 5839-6)

BS 5839-6 is the British Standard for fire detection in homes. It describes a system by its grade (how it's powered and how reliable it is) and its category (how much of the home it covers).

BS 5839-6 grades and categories in brief
CodeMeaning
Grade D1Mains-powered alarms with a sealed, built-in standby battery that lasts the life of the alarm
Grade D2Mains-powered alarms with a user-replaceable standby battery
Grade F1 / F2Battery-only alarms: F1 with a sealed long-life battery, F2 with a replaceable one
Category LD3Alarms in the escape route: hallways and landings
Category LD2LD3 plus the rooms where a fire is most likely to start, such as the living room and kitchen
Category LD1LD2 plus every room where a fire could start, except bathrooms and the like

In England, Approved Document B asks for at least a Grade D2, Category LD3 system in new homes, mains-powered with a standby supply and interlinked. Many designers go further, to LD2.

Mains-powered and interlinked

Interlinked means that when one alarm detects fire, they all sound, so someone asleep upstairs hears a fire that starts in the kitchen. Links can be wired (an extra core between alarms) or radio. Mains alarms are supplied from either their own dedicated circuit or a regularly used lighting circuit, as BS 5839-6 allows; a lighting circuit has the advantage that a fault there is noticed quickly. Mains alarms still have a standby battery so they work in a power cut.

Testing and replacing

  • Press the test button monthly. It checks the sounder and battery, and on interlinked systems that the others sound too.
  • Vacuum or dust the vents now and then, following the maker's instructions.
  • Replace alarms by the date on the label, usually 10 years after manufacture; the sensors degrade with age. CO alarms have a shorter or similar life: check the label.
  • If an alarm chirps, it's usually a low battery or the end of its life, not a fault to ignore.

What the law requires

Smoke, heat and CO alarm rules across Great Britain (homes)
NationWho it applies toWhat's required
EnglandLandlords of rented homesA smoke alarm on each storey with a room used as living accommodation (a bathroom or toilet counts), and a CO alarm in any room with a fixed combustion appliance, other than a gas cooker. Check they work on the first day of each new tenancy, and repair or replace them once told they're faulty (The Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended in 2022)
WalesLandlords under the Renting Homes (Wales) ActA smoke alarm on each storey that is in working order, connected to the mains and interlinked with every other mains smoke alarm; a CO alarm in each room with a gas, oil-fired or solid-fuel appliance (The Renting Homes (Fitness for Human Habitation) (Wales) Regulations 2022)
ScotlandEvery home, owned or rented, since 1 February 2022Smoke alarms in the living room (the room you spend most of the day in) and every hallway and landing, a heat alarm in every kitchen, all ceiling-mounted and interlinked; a CO alarm where there's a fixed combustion appliance, such as a boiler or wood burner. Alarms can be mains-wired or sealed, tamper-proof long-life lithium battery units (the tolerable standard, and Scottish Government guidance)

New homes, and major works such as extensions and loft conversions, also have to meet the building regulations in each nation, which ask for mains-powered, interlinked systems. Northern Ireland has its own rules.

Intermediate and advanced

Going deeper

Why heat alarms in kitchens

Cooking makes smoke and steam, so a smoke alarm in a kitchen goes off often. People then take its battery out or cover it, which is worse than no alarm. A heat alarm only responds to a high or quickly rising temperature, so it ignores toast but still warns of a pan fire, and because it's interlinked it wakes the whole house.

Coverage distances

BS 5839-6 sets how far any point in a room or hall can be from the nearest detector: in general 7.5 m for a smoke detector and 5.3 m for a heat detector. That means a long hallway or a big open-plan room may need more than one.

RCDs and smoke alarm circuits

Because mains alarms have a standby battery, an RCD trip doesn't stop them working, but the circuit arrangement should mean a trip is noticed and dealt with. If the alarms share a circuit with lighting, a trip leaves the lights off too, which people notice and fix. Follow BS 5839-6 and BS 7671 together when designing the supply.

Sources

The main references behind this guide. Numbers we worked out ourselves, such as the code outputs, come from running the code.