Scottish Building Standards cheat sheet for electricians ohmandtoken.com
Sockets and lighting (4.6)
- 13 A outlets, at least: 4 in each apartment; 6 in the kitchen (3 above worktop, plus any for white goods); 4 more anywhere, including 1 in each circulation area on every storey.
- A lighting point in every circulation space, kitchen, bathroom, toilet and any space of 2 m² or more. Stair lighting switched at each landing.
- Common stairs: 100 lux on flights and landings, 50 lux in other circulation areas. Door entry unit at a common entrance: 900 mm to 1.2 m.
Heights and positions (4.8.5)
| Fixture | Position |
|---|---|
| All outlets and controls | No higher than 1.2 m, at least 350 mm from an internal corner |
| Light switches | 900 mm to 1.1 m |
| Sockets, TV and phone outlets | At least 400 mm; at least 150 mm above a worktop |
| Sockets hidden behind white goods | Separate switching in an accessible place |
Fire detection (2.11), Grade D
- Smoke alarm in the principal habitable room (optical recommended), in every circulation space on each storey, and in any access room to an inner room. Heat alarm in every kitchen.
- Mains powered with standby, all interconnected. Own circuit at the board, or a separately protected, regularly used local lighting circuit.
- Circulation-space alarms: within 3 m of every bedroom door and 7 m of a living room or kitchen door.
- Ceiling mounted: smoke 25–600 mm below the ceiling and 300 mm from walls and lights; heat 25–150 mm below the ceiling.
Intermittent extract (Table 3.12)
| Room | Minimum rate |
|---|---|
| Kitchen, above hob | 30 l/s |
| Kitchen, elsewhere | 60 l/s |
| Utility room | 30 l/s |
| Bathroom or shower room | 15 l/s |
| Toilet | 6 l/s |
New dwelling with parking: an EV charge point socket of at least 7 kW (7.2). Electrical work in an existing house doesn't normally need a building warrant, but it must still meet the standards.
Sources:
- Scottish Government: Building standards technical handbook, domestic (April 2026)
Always check against your own copy of the current documents. Mains work must be carried out by a competent person.