Three phases
A three-phase supply has three line conductors, L1, L2 and L3, each carrying an AC voltage 120° (a third of a cycle) behind the one before. In the UK the voltage between any line and neutral is 230 V, and between any two lines it's 400 V. The 400 V is √3 (about 1.732) times 230 V, because the two line voltages are 120° apart, so you subtract them as phasors, not as plain numbers.
The big advantage is that three balanced loads draw a smooth, constant total power, so three-phase motors run smoothly and start themselves. It also moves more power per kilogram of copper than single-phase.
Star (Y)
In star, one end of each load joins at a common star point, and the other ends go to L1, L2 and L3. Each load gets the line-to-neutral voltage, 230 V. Each line feeds just one load, so the line current equals the load current.
Delta (Δ)
In delta, the loads form a triangle, each connected between two lines. Each load gets the full 400 V. Each line now feeds two loads, but their currents are 120° apart, so the line current is √3 times the load current, not twice it.
Why delta gives three times the power
Swap the same three loads from star to delta and each one gets √3 times the voltage. Power in a resistance goes with voltage squared, and √3 squared is 3. So the same heater elements make three times the heat in delta. Motor star-delta starters use exactly this: the motor starts in star, drawing a third of the current and torque, then switches to delta once it's up to speed.
The same total-power formula works for both connections:
P = √3 × VL × IL × power factor
where VL is the line voltage and IL the line current. A balanced 11 kW motor at 400 V and 0.85 power factor draws about 18.7 A per line.
Safety
400 V between lines is far more dangerous than 230 V to earth, and three-phase boards often have much higher fault levels. Three-phase work needs the right training, test equipment and safe isolation of every phase. Remember that the neutral of a three-phase system can carry current even when a single-phase circuit is switched off, which is the subject of the neutral current lab.
How this simulation works
The supply is a perfect, balanced 400 V, 50 Hz three-phase system, and the three loads are identical impedances with the power factor you set. The results are exact for that model. Real motors don't behave as fixed impedances: their current depends on the mechanical load. For more depth see three-phase power explained, and the star-delta converter for converting networks.