Three-phase power runs most of the world's motors and big heaters. Connect three loads in star or delta, and see how the same parts can give very different power.

Intermediate

L1L2L3star point

Challenges

  1. Connect three 53 Ω heater elements so they make about 9 kW (within 5%).
  2. Then connect the same three elements in star. What fraction of the power is left?
  3. Make a delta load draw a line current between 9.9 and 10.1 A at unity power factor.
  4. Model an 11 kW (within 3%) motor in delta at 0.85 power factor.

Controls

Readings

Three phases

A three-phase supply has three line conductors, L1, L2 and L3, each carrying an AC voltage 120° (a third of a cycle) behind the one before. In the UK the voltage between any line and neutral is 230 V, and between any two lines it's 400 V. The 400 V is √3 (about 1.732) times 230 V, because the two line voltages are 120° apart, so you subtract them as phasors, not as plain numbers.

The big advantage is that three balanced loads draw a smooth, constant total power, so three-phase motors run smoothly and start themselves. It also moves more power per kilogram of copper than single-phase.

Star (Y)

In star, one end of each load joins at a common star point, and the other ends go to L1, L2 and L3. Each load gets the line-to-neutral voltage, 230 V. Each line feeds just one load, so the line current equals the load current.

Delta (Δ)

In delta, the loads form a triangle, each connected between two lines. Each load gets the full 400 V. Each line now feeds two loads, but their currents are 120° apart, so the line current is √3 times the load current, not twice it.

Why delta gives three times the power

Swap the same three loads from star to delta and each one gets √3 times the voltage. Power in a resistance goes with voltage squared, and √3 squared is 3. So the same heater elements make three times the heat in delta. Motor star-delta starters use exactly this: the motor starts in star, drawing a third of the current and torque, then switches to delta once it's up to speed.

The same total-power formula works for both connections:

P = √3 × VL × IL × power factor

where VL is the line voltage and IL the line current. A balanced 11 kW motor at 400 V and 0.85 power factor draws about 18.7 A per line.

Safety

400 V between lines is far more dangerous than 230 V to earth, and three-phase boards often have much higher fault levels. Three-phase work needs the right training, test equipment and safe isolation of every phase. Remember that the neutral of a three-phase system can carry current even when a single-phase circuit is switched off, which is the subject of the neutral current lab.

How this simulation works

The supply is a perfect, balanced 400 V, 50 Hz three-phase system, and the three loads are identical impedances with the power factor you set. The results are exact for that model. Real motors don't behave as fixed impedances: their current depends on the mechanical load. For more depth see three-phase power explained, and the star-delta converter for converting networks.