Home / Circuit lab / Neutral current and broken neutral

Three-phase neutral current and broken neutral simulator

Three single-phase loads share one neutral. Balance them and the neutral carries nothing. Unbalance them, then break the neutral, and see why a lost neutral destroys equipment.

Advanced

L1L2L3Nneutral broken

Challenges

  1. Load all three phases with at least 3 kW each and get the neutral current under 0.5 A.
  2. Load only L1 and L2 equally (at least 2 kW each). Compare the neutral current with each line current.
  3. Break the neutral and push one load over 300 V.
  4. Show that balanced loads cancel whatever their power factor: all three at 4 kW, power factor below 0.9, neutral current under 0.5 A.

Controls

Readings

What the neutral carries

Most buildings with a three-phase supply split their single-phase circuits across L1, L2 and L3, all returning on one shared neutral. The neutral carries the phasor sum of the three line currents. Because the currents are 120° apart, they partly cancel. If all three are equal, they cancel completely and the neutral carries nothing at all.

With unequal loads, the neutral carries the imbalance. Load only L1 and L2 equally and the neutral current equals each line current, because two equal currents 120° apart add up to one of the same size. Load only one phase and the neutral carries all of that current. That's why designers spread single-phase loads evenly across the phases, and why a well-balanced building has a small neutral current.

The phasor diagram

The grey arrows are the three line-to-neutral voltages, 230 V and 120° apart. The orange arrows are the line currents, each in step with its voltage for resistive loads, or lagging it for inductive ones. The red arrow is their sum, the neutral current. Balanced loads at any power factor still cancel, because all three currents shift by the same angle.

When the neutral breaks

If the shared neutral is lost, for example a failed joint in the supply cable, the single-phase loads are no longer connected to the star point. They are effectively in series across the 400 V between lines. The star point floats to wherever the loads balance it, and each load's voltage now depends on how heavily the phases are loaded:

  • The lightly loaded phase gets a high voltage, approaching 400 V. Its equipment can be destroyed in seconds, and surge protection and electronics often fail first.
  • The heavily loaded phase gets a low voltage, so motors stall and overheat.

The UK statutory supply limits are 230 V +10% / −6%, which is 216.2 V to 253 V. A broken neutral can push loads far outside that. On a PME (TN-C-S) supply, where the neutral and earth are combined in the supply cable, a broken PEN conductor can also make earthed metalwork live, which is why PME has special rules for bonding and for outdoor equipment such as electric vehicle chargers. Our guide to earthing systems explains PME.

Harmonics

This simulation uses pure sine wave currents. Computers, LED drivers and other electronic loads draw distorted current containing harmonics. The third harmonic and its multiples don't cancel in the neutral: they add up. In buildings full of IT equipment, the neutral current can approach or even exceed the line currents, so BS 7671 requires the neutral to be sized for it. A real installation's neutral may need to be bigger than this model suggests.

How this simulation works

Each load is a fixed impedance sized to draw its rated power at 230 V and the power factor you set, on a perfect, balanced 400/230 V supply. With the neutral broken, the star point voltage is found with Millman's theorem, and every voltage and current is exact for fixed impedances. Real equipment isn't a fixed impedance: electronic power supplies draw more current as the voltage falls, which can make a broken neutral even worse. See three-phase power explained for the basics.