Why voltage drops along a cable
Copper is a very good conductor, but not a perfect one. A 2.5 mm² conductor has about 7.4 mΩ of resistance per metre at 20 °C, and more when it's warm. Current has to flow out along the line conductor and back along the neutral, so both lose a little voltage. On a long run carrying a big current, that adds up to several volts, and the load gets less than 230 V.
A low voltage makes motors run hotter, lamps dimmer and some electronics misbehave. It also means power is being wasted as heat in the cable, which is the voltage drop times the current.
The mV/A/m method
BS 7671 Appendix 4 tabulates a voltage drop for each cable size in millivolts per amp per metre (mV/A/m). For single-phase circuits it already includes both the line and the neutral conductor, at the cable's full operating temperature. For flat twin and earth (Table 4D5) the values are:
| Size (mm²) | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | 16 |
|---|---|---|---|---|---|---|---|
| mV/A/m | 44 | 29 | 18 | 11 | 7.3 | 4.4 | 2.8 |
voltage drop = mV/A/m × design current × length ÷ 1000
So 25 m of 4 mm² carrying 32 A drops 11 × 32 × 25 ÷ 1000 = 8.8 V.
The limits
For an installation fed from a public low voltage supply, Appendix 4 gives limits from the origin of the installation to the load: 3% for lighting (6.9 V) and 5% for other uses (11.5 V). They're there to make sure equipment gets a voltage within its working range, and they're used as the normal design criteria in the UK. Bigger installations with a private supply, such as their own transformer, are allowed 6% and 8%.
The two challenges for lighting show how quickly long runs catch you out: 40 m at 6 A on 1.5 mm² drops 6.96 V, just over the 6.9 V limit.
Voltage drop isn't the only check
When sizing a cable, voltage drop is one of several checks. The cable must also carry the design current without overheating, allowing for how it's installed, covered in insulation or grouped with others. The earth fault loop impedance must be low enough for the protective device to disconnect in time (see the earth fault loop lab). And it must withstand the fault current. Any one of these can decide the size.
The tabulated values assume the conductor is running at its maximum temperature, 70 °C for thermoplastic cable. If the cable is lightly loaded it runs cooler and the real drop is a little less. BS 7671 Appendix 4 shows how to correct for that, which can make the difference on a borderline run.
How this simulation works
The drop is the BS 7671 Table 4D5 single-phase value times the current and length, as a designer would calculate it, shared equally between line and neutral in the drawing. The supply is taken as exactly 230 V at the board, and the voltage drop in the supply itself isn't included. For a full cable design including current-carrying capacity and correction factors, use the cable sizing calculator, or the voltage drop calculator for other cable types.