Every electrician's most important test is the one that proves a circuit is dead before they touch it. That needs three things: a two-pole voltage indicator, a proving unit to check the indicator works, and locks to keep the circuit isolated while you work. This guide explains what to look for in each, and compares the indicators electricians actually carry.
The short answer
- For most electricians, a GS38-compliant two-pole indicator made to BS EN 61243-3, a matching proving unit, and a lock-off kit for the breakers you meet. Buying them as a kit is usually cheaper.
- If you want no batteries to go flat, the Martindale VI-13800 and VI-15000 are powered from the circuit under test.
- If you also want continuity, phase rotation and a numeric display, look at the Fluke T150 or Megger TPT420.
- Never use a multimeter, a socket tester or a non-contact detector to prove dead.
Our picks: professional, mid-range and entry
Some shop links are affiliate links (Amazon UK, Tooled Up): if you buy through one we may earn a small commission, at no extra cost to you. As an Amazon Associate I earn from qualifying purchases. It never changes which products we recommend, and no shop has paid to be included.
Martindale VI-15000 (or the VIPDLOK150-S kit)
Anyone who wants a self-powered indicator rated for every installation category.
- CAT IV 1000 V, to BS EN 61243-3 and GS38
- LED thresholds at 50, 120, 230, 400 and 690 V, AC and DC
- Powered from the circuit under test: no batteries
- Response under 0.1 s; test current under 3.5 mA
- Kit version adds the PD690S proving unit and a lock-out kit
Why we picked it: No batteries, ranges or switches to get wrong, and the highest safety rating here.
Martindale VI-13800
Domestic and commercial electricians on 230/400 V systems.
- CAT IV 600 V, to BS EN 61243-3 and GS38
- LED thresholds at 50, 100, 200 and 400 V, AC and DC
- Self-powered: no batteries
- Retractable locking probe shrouds
Kewtech KT1780 (with KEWPROVE 3)
A lower-cost LED indicator that also checks continuity and phase rotation.
- 12 to 690 V AC/DC on LEDs
- CAT IV 600 V, CAT III 690 V, IP65
- Continuity test and phase rotation
- To IEC 61243-3, with GS38 probe tips
Watch out: Battery-powered (two AAA). The KEWPROVE 3 proving unit is sold separately or in kits.
Fluke T150 with PRV240 proving unit
Electricians who want a display, continuity, resistance and phase rotation in one tester.
- 6 to 690 V AC/DC with LCD
- Continuity 0 to 400 kΩ, resistance up to 1999 Ω
- Phase rotation 100 to 690 V
- Switchable load (7 kΩ) to rule out ghost voltages
- CAT III 690 V, CAT IV 600 V, IP64
Watch out: Uses two AAA batteries. The PRV240 sources 240 V AC or DC, which proves the tester on its lower ranges only.
Check price atRS
| Tier | Model | Best for | Key spec |
|---|---|---|---|
| Professional | Martindale VI-15000 | Self-powered, all categories | CAT IV 1000 V |
| Mid-range | Martindale VI-13800 | 230/400 V work, no batteries | CAT IV 600 V |
| Entry | Kewtech KT1780 | Budget LED tester | 12 to 690 V, CAT IV 600 V |
| Also consider | Fluke T150 | Display, ohms, phase rotation | 6 to 690 V, CAT IV 600 V |
| Also consider | Megger TPT420 | PV and high DC | 1500 V DC, CAT IV 1000 V |
All figures are from each manufacturer's datasheet. A note on the Kewtech KT1790: it's the LCD version of the KT1780, and Kewtech has since introduced the KT1795, so check which is current before you buy.
What to look for in a voltage indicator
Made to BS EN 61243-3
BS EN 61243-3 is the product standard for two-pole low-voltage detectors. It sets how the indicator must show a dangerous voltage, how it must behave at its limits, and it doesn't allow fuses in the leads: protection comes from high-value resistors in the probe instead, as Martindale's datasheet explains. A meter that's "safe to CAT III" isn't the same thing.
GS38 probes and leads
HSE guidance GS38 asks for finger guards, insulated leads in good condition, and no more than 4 mm of exposed tip, preferably 2 mm or less, or spring-loaded shrouds. Fixed leads that can't be swapped for the wrong ones are a plus.
Self-powered or battery
A self-powered indicator such as the Martindale VI series has nothing to go flat. Battery testers can add a display, continuity and phase rotation. Megger states the TPT420 still warns of dangerous voltages with exhausted batteries; check that claim for any battery tester you consider.
Voltage range and category
Choose an indicator rated above the highest voltage you'll meet, including DC on solar and battery systems, and at the right installation category. CAT IV is needed at the supply origin.
Low current draw
Most indicators draw a few milliamps at most (under 3.5 mA in the datasheets above), so testing line to earth won't trip a 30 mA RCD. The Fluke T-range's switchable load deliberately draws more, which helps rule out induced "ghost" voltages.
Proving units
A proving unit is a small, battery-powered voltage source. You prove the indicator on it before and after the test, which shows it was working throughout. Match the proving unit to your indicator: it has to drive the indicator's top LEDs, or you only prove the bottom of its range. Martindale's PD690S is designed for 690 V indicators; Fluke's PRV240 sources 240 V AC or DC for both high and low impedance testers.
Lock-off kits
A lock-off kit holds a breaker, fuse carrier or isolator in the off position so nobody can switch it back on while you work. A good kit has:
- MCB locks to fit the breakers you meet: the clip widths differ, so a kit with several sizes helps.
- A padlock with a unique key that only you hold.
- A hasp, so several people can each fit their own lock.
- "Equipment locked out" tags to write on.
Martindale's LOKKIT1, for example, includes a padlock with a unique key, a hasp for up to six padlocks, MCB locks with 6 mm and 10 mm clips, tags and a marker pen.
Before you buy: a quick checklist
- Made to BS EN 61243-3, with GS38 probes (shrouds or 4 mm maximum exposed tip).
- Rated above the highest voltage you'll meet, AC and DC, at the right CAT.
- A proving unit that drives your indicator's top range.
- Locks that fit the breakers and fuse carriers you work on, plus your own padlock and key.
- A routine check that the leads, probes and case are undamaged, and a calibration check as your scheme or employer requires.
Questions people ask
Can I use a multimeter to prove dead?
Is a voltage pen (non-contact detector) enough?
Why prove the indicator after the test as well?
Do I need a separate proving unit if I have a known live supply?
Related guides
Our safe isolation procedure walks through each step. For testing after isolation, see our guides to insulation testers and multifunction testers.
Sources
The main references behind this guide.
- Electrical Safety First Best Practice Guide 2: Safe isolation (Issue 4.2, 2024)
- HSE GS38: Electrical test equipment for use on low voltage electrical systems
- Martindale VI-13800 and VI-15000 technical data
- Martindale VIPD150-S and lock out kits technical data (Farnell copy)
- Martindale LOKKIT1 lock out kit technical data
- Fluke T90/T110/T130/T150 technical data, with PRV240 proving unit (Farnell copy)
- Megger TPT420 voltage tester datasheet
- Kewtech KT1780 product data sheet (Farnell copy)
- Kewtech KT1790 product data sheet