Why rings are tested this way
A ring final circuit starts at the board, loops through every socket and returns to the same breaker. The current can reach each socket two ways, which lets 2.5 mm² cable carry a 32 A circuit. But that only works if the ring is complete. A break turns it into two long radials, each of which could be overloaded, and the circuit would still work normally, so nobody would notice. The test proves the ring is continuous and correctly connected, and it gives you the R1 + R2 value at the same time.
Step 1: end to end
With the circuit isolated, separate the two ends at the board and measure the resistance of each conductor from one end to the other: line (r1), neutral (rn) and circuit protective conductor (r2). For 2.5/1.5 mm² twin and earth, r1 and rn should match within 0.05 Ω, and r2 should be about 1.67 times bigger, because the 1.5 mm² cpc has more resistance per metre (12.10 against 7.41 mΩ per metre at 20 °C). An open-circuit reading means a break.
Step 2: line and neutral cross-connected
Join the line of one end to the neutral of the other end, and the other line to the first neutral. Then measure between line and neutral at every socket. On a healthy ring every socket reads the same, about (r1 + rn) ÷ 4, within 0.05 Ω. Here's why: at any socket there are two paths between L and N through the figure-of-eight, and together they always add up to the full length of one conductor. The two halves in parallel give a quarter of the end-to-end loop.
Step 3: line and cpc cross-connected
Do the same with line and cpc, and measure between them at every socket. This time the readings are close to (r1 + r2) ÷ 4. Because the cpc is smaller than the line conductor, the sockets near the ends read slightly lower and the middle of the ring reads highest. You record the highest reading as the circuit's R1 + R2, and it also proves the polarity at each socket.
What the faults look like
- Ends joined the wrong way (L1 to N1 instead of L1 to N2): the readings are low near the ends and rise towards the middle. Swap the cross-connection and test again.
- A broken conductor: step 1 reads open circuit. If you go on to step 2 anyway, the sockets all read about double the expected value, because there's only one path.
- An interconnection, an extra cable joining two points of the ring (sometimes a "bridge" from an old alteration): the end-to-end readings look a little low, and at steps 2 and 3 the readings vary round the ring, lowest near the interconnection.
How this simulation works
The ring is modelled as 2.5/1.5 mm² copper with the IEC 60228 maximum resistances at 20 °C and ten equally spaced sockets. Every reading is found by solving the whole resistor network exactly, including the cross-connections and faults, so the patterns are real, not drawn. Real readings include the test lead resistance, so null your leads first, and connection resistance at each terminal adds a little. Always follow safe isolation before testing. Our guides to ring final circuit testing and R1 + R2 testing go through the full procedure, and the ring final calculator works out expected values.