164 circuit diagram and wiring layout symbols, drawn clearly, with the IEC (UK) and US versions side by side. Search them, copy any symbol for your own drawings, or test yourself.
A connection between parts. Its length on the drawing means nothing.
Used everywhere
Wires joined
A dot shows wires that are connected.
Draw joins as T-junctions with a dot. A four-way join is clearer staggered into two Ts.
IEC / UKUS
Wires crossing, not joined
Two wires that cross on the drawing but don't connect.
Some older drawings use a small hop (the US version shown) to make this obvious. If wires cross with no dot, they are not joined.
Used everywhere
Terminal
A point where a wire is connected, such as a screw terminal.
Used everywhere
Earth (ground)
A connection to the general mass of earth, or to the earthing system.
In electronics, GND is often just the 0 V reference and may not be connected to earth at all.
Used everywhere
Protective earth
The protective earth (PE) connection, for safety. Marks the PE terminal on equipment.
Used everywhere
Frame or chassis
A connection to the metal frame or case of equipment.
IEC 60617
Neutral conductor (N)
Marks a conductor on a single-line drawing as the neutral.
A conductor marked with this, the PE mark and three short strokes is a 3-phase, neutral and earth circuit (see the next symbols).
IEC 60617
Protective conductor (PE)
Marks a conductor on a single-line drawing as the protective (earth) conductor.
IEC 60617
PEN conductor (combined earth and neutral)
A combined protective and neutral conductor, as in a TN-C-S (PME) supply cable.
Not normally allowed in a consumer's installation in the UK (ESQCR regulation 8(4)); on a PME supply it ends at the supply intake.
IEC 60617
Three conductors
Three conductors drawn as one line on a single-line drawing, one stroke for each.
For many conductors draw one stroke and write the number beside it.
IEC 60617
Three phases, neutral and earth
A five-core circuit (L1, L2, L3, N and PE) shown as a single line.
IEC 60617
Underground cable
A cable laid underground.
IEC 60617
Overhead line
A conductor carried overhead on poles.
IEC 60617
Plug and socket
A plug-in connection. The solid pin is the plug (male); the curve is the socket (female).
IEC 60417
Functional earth
An earth connection needed for equipment to work properly, such as a clean signal earth, rather than for safety (IEC 60417-5018).
IEC 60417
Equipotential bonding
Parts joined so they are at the same voltage, such as an equipotential bonding terminal (IEC 60417-5021).
Cells, batteries and supplies
Used everywhere
Cell
A single cell. The long line is positive, the short thick line negative.
Draw the short line thicker, as here. A battery is two or more cells.
Used everywhere
Battery
Several cells in series. The dashed line means more cells than are drawn.
Write the voltage beside it, for example 9 V.
Used everywhere
DC voltage source
An ideal DC supply that holds its voltage whatever the current.
Used everywhere
AC supply
An AC voltage source, such as the mains or a signal generator.
Used everywhere
Current source
An ideal source that drives a set current whatever the voltage.
Used everywhere
Solar (PV) cell
A photovoltaic cell: a cell that makes electricity from light.
Resistors, capacitors, coils and fuses
IEC / UKUS
Resistor
Limits current. The box is the IEC and UK symbol; the zigzag is the US one.
The value is written beside it, for example 220R or 4k7.
IEC / UKUS
Variable resistor (rheostat)
A resistor whose value can be changed.
IEC / UKUS
Potentiometer
A resistor with a sliding contact (wiper): three connections. Used as a volume control or adjustable divider.
IEC / UKUS
Preset (trimmer) resistor
A resistor set once with a screwdriver, then left.
IEC / UKUS
Thermistor
A resistor whose value changes with temperature. −t° marks an NTC type (resistance falls as it warms); +t° a PTC.
IEC / UKUS
Light dependent resistor (LDR)
A resistor whose resistance falls as more light falls on it.
Older drawings put it in a circle.
Used everywhere
Heating element
A resistance used to make heat, such as an immersion heater element.
Used everywhere
Capacitor
Stores charge. Two plates with a gap.
IEC / UKUS
Polarised (electrolytic) capacitor
A capacitor that must be connected the right way round: + to the more positive side.
Fitted backwards, an electrolytic can overheat and burst.
Used everywhere
Variable capacitor
A capacitor whose value can be changed, as used in old radio tuners.
Used everywhere
Inductor (coil)
A coil of wire that stores energy in a magnetic field and resists changes in current.
Used everywhere
Inductor with magnetic core
A coil wound on iron or ferrite, which gives far more inductance.
Used everywhere
Transformer
Two coils on a shared core. Changes AC voltage up or down; also isolates one side from the other.
IEC also allows two overlapping circles for a transformer, common on power drawings.
IEC / UKUS
Fuse
A wire that melts to break the circuit if too much current flows.
Used everywhere
Resistor with a fixed tap
A resistor with an extra connection part-way along it.
IEC 60617
Shunt (four-terminal resistor)
A low-value resistor with separate terminals for measuring the voltage across it, used to measure large currents.
Used everywhere
Varistor (VDR, MOV)
A resistor whose resistance falls sharply above a set voltage. Used to absorb surges, for example in surge protection devices.
IEC 60617
Feed-through capacitor
A capacitor built around a conductor passing through a metal panel, used to filter interference (IEC 60617 04-02-03).
Used everywhere
Preset (trimmer) capacitor
A capacitor set once with a tool, then left.
Used everywhere
Inductor with a tap
A coil with an extra connection part-way along its winding.
Used everywhere
Variable inductor
A coil whose inductance can be changed.
Used everywhere
Quartz crystal
A piezoelectric crystal that resonates at a very precise frequency. Sets the clock in microcontrollers and watches.
IEC 60617
Transformer (power drawing form)
A two-winding transformer drawn as two overlapping circles, the usual form on power and single-line drawings.
IEC 60617
Transformer, delta-star (Dyn)
A three-phase transformer with a delta primary and star secondary, as on most UK 11 kV to 400 V distribution transformers.
The secondary star point gives the neutral.
IEC 60617
Current transformer (CT)
Measures a large current by passing the conductor through a ring core. The secondary gives a small proportional current, such as 5 A or 1 A.
Never open-circuit a CT secondary while the primary is carrying current: the voltage can rise to dangerous levels.
IEC 60617
Voltage transformer (VT)
A small transformer that steps a high voltage down to a measurable one, such as 110 V, for meters and protection relays.
Diodes, transistors and ICs
Used everywhere
Diode
Lets current flow one way only, in the direction of the arrow (anode to cathode). The bar is the cathode.
The cathode end of a real diode is marked with a band.
Used everywhere
LED
A light-emitting diode: a diode that gives out light when current flows through it.
Always needs something to limit its current, usually a resistor.
Used everywhere
Zener diode
Used in reverse to hold a fixed voltage, such as 5.1 V.
Write the voltage beside it.
Used everywhere
Schottky diode
A fast diode with a low forward voltage, about 0.2 to 0.4 V.
Used everywhere
Photodiode
A diode that lets a current through in proportion to the light falling on it.
Used everywhere
NPN transistor
A bipolar transistor. A small base current switches or controls a larger collector current. The arrow on the emitter points out.
Collector at the top, emitter at the bottom, base on the left.
Used everywhere
PNP transistor
Like an NPN but with the polarities reversed. The arrow on the emitter points in.
Memory aid: PNP, Pointing iN Permanently.
Used everywhere
N-channel MOSFET
A voltage-controlled transistor. A positive gate-source voltage turns it on. The broken line means enhancement mode (off with 0 V on the gate).
Many symbols also show the body diode.
Used everywhere
Thyristor (SCR)
A diode that only starts conducting when its gate is triggered, then stays on until the current falls to near zero.
Used everywhere
Triac
Two thyristors back to back with one gate: switches AC both ways. Used in light dimmers.
Used everywhere
Op-amp
An amplifier with two inputs, inverting (−) and non-inverting (+). Power connections are often left off the drawing.
Used everywhere
Bidirectional TVS (transient suppressor)
Two breakdown diodes back to back. Clamps voltage spikes in either direction.
Used everywhere
Diac
Conducts in either direction once the voltage across it passes its breakover voltage (about 30 V). Used to trigger triacs.
Like a triac with no gate.
Used everywhere
Varicap (tuning) diode
A diode used reverse-biased as a capacitor whose value changes with voltage. Used for tuning.
Used everywhere
Phototransistor
A transistor switched on by light falling on its base, so it often has no base lead.
Used everywhere
Optocoupler (opto-isolator)
An LED and a phototransistor in one package. The signal crosses by light, so the two sides stay electrically isolated.
Used to pass signals safely between mains and low-voltage circuits.
Used everywhere
N-channel JFET
A junction field-effect transistor. On with 0 V on the gate; a negative gate voltage pinches it off. The arrow points in for N-channel.
Used everywhere
P-channel JFET
Like the N-channel JFET with polarities reversed. The arrow points out.
Used everywhere
P-channel MOSFET
A MOSFET turned on by taking the gate negative of the source. The arrow points away from the channel for P-channel.
Often used as a high-side switch.
Used everywhere
N-channel MOSFET, depletion mode
A MOSFET that is on with 0 V on the gate. The solid channel line marks depletion mode.
Used everywhere
IGBT
Insulated-gate bipolar transistor: a gate like a MOSFET driving a bipolar output. Switches high power in inverters, VSDs and EV chargers.
Terminals: gate, collector, emitter.
Used everywhere
Bridge rectifier
Four diodes that turn AC into DC. AC goes in at the two ~ corners; DC comes out at + and −.
Often drawn as a box with ~, + and − terminals.
Used everywhere
Voltage regulator
A linear regulator, such as a 7805, that gives a steady output voltage from a higher input.
Usually needs a small capacitor on the input and output.
Switches, relays and breakers
Used everywhere
Switch (on/off)
A single-pole, single-throw switch: makes or breaks one circuit.
Used everywhere
Changeover switch (SPDT)
Connects the common terminal to one of two others. Two of these make two-way lighting.
Used everywhere
Push-to-make button
Makes the circuit only while it's pressed (normally open), like a doorbell button.
Used everywhere
Push-to-break button
Breaks the circuit while it's pressed (normally closed), like a stop button.
Used everywhere
Relay (coil and contact)
A coil that, when energised, operates one or more contacts. The dashed line links the coil to its contact.
On control drawings the coil and contacts are often drawn apart, labelled with the same name (K1, KA1).
Used everywhere
Circuit-breaker
A switch that opens automatically on overcurrent, and can be reset.
The cross at the fixed contact is what marks it as a circuit-breaker.
Switchgear, fuses and protection
IEC 60617
Fuse, supply side marked
A fuse with a thick end showing which side the supply is connected to (the side that stays live when the fuse is removed).
IEC 60617
Disconnector (isolator)
An isolating switch, opened off load to make a circuit safe to work on. The short bar on the fixed contact marks the disconnector function.
Not designed to break load current: open the circuit first.
IEC 60617
Switch-disconnector
A switch that can make and break load current and also isolates. The small circle marks the switch-disconnector function.
A typical main switch in a consumer unit.
IEC 60617
Contactor (main contact)
A power contact worked by a coil, used to switch motors, heating and lighting. The semicircle marks the contactor function.
The coil is drawn elsewhere on the control circuit with the same label, such as KM1.
IEC 60617
Fuse-switch
A switch whose moving part carries the fuse, so opening it removes the fuse from the circuit.
IEC 60617
Fuse-disconnector
A fuse carrier that acts as a disconnector: pull it out, off load, to isolate.
IEC 60617
Fuse switch-disconnector
A switch-disconnector with fuses in its moving part. Can be opened on load. Common as the main switch on larger boards.
IEC 60617
Earthing switch
A switch that connects a conductor to earth, used on high-voltage switchgear to earth a circuit before work.
Drawn closed only when the circuit is earthed.
IEC 60617
Surge arrester
Diverts a voltage surge, such as from lightning, safely to earth.
On a drawing it's usually connected between a line and earth.
IEC 60617
Spark gap
Two electrodes with a gap that flashes over at a set voltage.
IEC 60617
Gas discharge arrester
A spark gap sealed in a gas-filled tube. The dot marks the gas filling. Used to protect telecom and data lines.
Control circuit contacts, coils and timers
IEC 60617
Make contact (normally open, NO)
Open at rest, closes when operated. In control circuits it's drawn vertically like this.
Contactor and relay auxiliary NO contacts are usually numbered 13-14, 23-24 and so on.
IEC 60617
Break contact (normally closed, NC)
Closed at rest, opens when operated.
NC auxiliary contacts are usually numbered 11-12, 21-22 and so on. Stop buttons use NC contacts.
IEC 60617
Change-over contact
One moving contact that switches between two fixed contacts, breaking one before making the other.
Relay terminals are often 11 (common), 12 (NC) and 14 (NO).
IEC 60617
Contactor contact, normally open
A make contact with the contactor semicircle. Main power contacts are numbered 1-2, 3-4, 5-6.
IEC 60617
Contactor contact, normally closed
A break contact with the contactor semicircle.
IEC 60617
Limit (position) switch, NO
A make contact worked by a moving part of the machine, such as a guard or an end stop. The wedge marks a position switch.
IEC 60617
Limit (position) switch, NC
A break contact worked by a moving part of the machine, often used as a safety stop.
IEC 60617
On-delay timer contact, NO
Closes a set time after the timer coil is energised; opens straight away when it's de-energised.
IEC rule: the delay acts when the contact moves towards the centre of the curve, like a parachute.
IEC 60617
Off-delay timer contact, NO
Closes straight away when the timer coil is energised; opens a set time after it's de-energised.
IEC 60617
On-delay timer contact, NC
Opens a set time after the timer coil is energised; closes straight away when it's de-energised.
IEC 60617
Push button, NO (start)
A push-button make contact, such as a start button. The dashed line links the contact to the push operator (the bracket).
Start buttons are usually green or white and wired with a contactor hold-in (latching) contact across them.
IEC 60617
Push button, NC (stop)
A push-button break contact, such as a stop button. Breaks the circuit while pressed.
Stop buttons use NC contacts so a broken wire stops the machine rather than leaving it unable to stop.
IEC 60617
Emergency stop (mushroom head)
A mushroom-head push button with an NC contact. Emergency stops latch down until twisted or pulled to reset.
Drawing practice varies; the legend on the drawing will say which actuator mark is used.
IEC 60617
Relay or contactor coil
The operating coil of a relay or contactor. Its contacts are drawn elsewhere with the same label, such as K1.
Coil terminals are A1 and A2.
IEC 60617
Timer coil, on-delay (slow to operate)
A coil whose contacts operate a set time after it's energised.
IEC 60617
Timer coil, off-delay (slow to release)
A coil whose contacts release a set time after it's de-energised.
IEC 60617
Remanent (latching) relay coil
A relay that stays in its last position after the coil current stops.
IEC 60617
AC relay coil
A relay or contactor coil for an AC supply.
IEC 60617
Thermal overload relay
The heater element of a motor overload relay, which trips when too much current flows for too long.
Its NC contact (95-96) is wired in the contactor coil circuit.
Lamps, motors, sound and meters
Used everywhere
Lamp
A lamp or indicator light.
The same cross-in-a-circle is the IEC symbol for any lamp.
Used everywhere
Motor
An electric motor. A small ~ or 3~ under the M shows AC or three-phase.
Used everywhere
Generator
A generator or alternator.
Used everywhere
Buzzer
Makes a sound when powered.
Used everywhere
Loudspeaker
Turns an electrical signal into sound.
Used everywhere
Microphone
Turns sound into an electrical signal.
Used everywhere
Voltmeter
Measures voltage. Connected across (in parallel with) the part.
Used everywhere
Ammeter
Measures current. Connected in series, so the current flows through it.
Used everywhere
Ohmmeter
Measures resistance, with the circuit dead.
IEC 60617
Indicator (signal) lamp
A pilot or indicator lamp, as on a control panel. Labelled H1, H2 on control drawings.
Used everywhere
Wattmeter
Measures power.
IEC 60617
Energy meter (kWh)
Measures energy used, such as the supply meter. Integrating (adding-up) instruments are drawn as rectangles.
Used everywhere
Frequency meter
Measures frequency.
Used everywhere
Galvanometer
A very sensitive current meter, used to show tiny currents or a balance point.
Used everywhere
Three-phase motor
A three-phase AC motor, with its three supply connections.
Used everywhere
Single-phase motor
A single-phase AC motor, such as a fan or pump motor.
Used everywhere
Three-phase generator
A three-phase generator or alternator, such as a standby generator.
Used everywhere
Antenna (aerial)
A radio antenna.
Logic gates
IEC / UKUS
AND gate
Output is 1 only when all inputs are 1.
The rectangle with a symbol inside is the IEC form; the shaped symbol is the traditional US form, still very common.
IEC / UKUS
OR gate
Output is 1 when any input is 1.
IEC / UKUS
NOT gate (inverter)
Output is the opposite of the input. The small circle means inversion.
IEC / UKUS
NAND gate
AND followed by NOT: output is 0 only when all inputs are 1.
IEC / UKUS
NOR gate
OR followed by NOT: output is 1 only when all inputs are 0.
IEC / UKUS
XOR gate (exclusive OR)
Output is 1 when the inputs are different.
IEC / UKUS
XNOR gate
Output is 1 when the inputs are the same.
IEC / UKUS
Buffer
Output equals the input. Used to boost drive or isolate stages.
IEC / UKUS
Schmitt trigger input
A gate with hysteresis: it switches at a higher voltage going up than going down, so slow or noisy signals give a clean output.
IEC / UKUS
Tri-state buffer
Passes the input when enabled (EN); otherwise its output goes high-impedance, as if disconnected. Lets several outputs share one bus.
The triangle pointing down marks a three-state output in IEC form.
Used everywhere
D flip-flop
Stores one bit. On the clock edge (C, the triangle marks edge-triggered), the output Q takes the value on D. Q̄ is its opposite.
Used everywhere
SR latch
Set (S) makes Q go to 1 and stay there; Reset (R) makes it 0. A one-bit memory, like a start/stop latch in software.
Used everywhere
JK flip-flop
Like a D flip-flop with two inputs. J=1 sets, K=1 resets, both 1 toggles the output on each clock edge. Used in counters.
Wiring layout (installation) drawings
IEC 60617
Socket outlet
A power socket outlet on a wiring layout drawing (IEC 60617 S00457).
On a plan, the flat side of the half-circle faces the wall.
IEC 60617
Multiple socket outlet
A multiple socket outlet, the number giving how many (IEC 60617 S00458). Here, a double socket.
IEC 60617
Socket outlet with protective contact
A socket outlet with an earth contact (IEC 60617 S00460). All UK BS 1363 sockets have one.
IEC 60617
Switched socket outlet
A socket outlet with a single-pole switch (IEC 60617 S00462).
UK switched sockets are usually double-pole; the drawing legend says which.
IEC 60617
Switch (one-way)
A light switch on a layout drawing (IEC 60617 S00466, on/off switch).
IEC 60617
Two-pole switch
A switch that breaks two poles, such as line and neutral (IEC 60617 S00469).
IEC 60617
Two-way switch
A two-way single-pole switch, used in pairs to control a light from two places (IEC 60617 S00471).
IEC 60617
Dimmer
A dimmer switch (IEC 60617 S00473).
IEC 60617
Pull-cord switch
A ceiling pull-cord switch, as used in UK bathrooms (IEC 60617 S00474).
IEC 60617
Lighting point
Where a light fitting goes (IEC 60617 S00481, lighting outlet position). The line is the wiring to it.
IEC 60617
Wall light point
A lighting point on a wall (IEC 60617 S00482).
IEC 60617
Fluorescent or linear luminaire
A fluorescent lamp or luminaire (IEC 60617 S00484). Drawn to its length on the plan.
IEC 60617
Self-contained emergency light
A self-contained emergency lighting luminaire with its own battery (IEC 60617 S00492).
IEC 60617
Junction box
A connection or junction box (IEC 60617 S00454).
IEC 60617
Distribution board
A distribution centre: a consumer unit or distribution board (IEC 60617 S00456).
IEC 60617
Supply intake
The consumer's terminal or service entrance equipment, where the supply comes in (IEC 60617 S00455).
IEC 60617
Three-phase socket outlet
A three-phase socket with neutral and earth, such as a 5-pin industrial (BS EN 60309) socket.
IEC 60617
Telecom or data socket
A telecommunications outlet. Letters say which kind: TP for telephone, TV for television, and so on. Check the drawing legend.
IEC 60617
Intermediate switch
An intermediate switch, wired between two two-way switches to control a light from three or more places.
IEC 60617
Switch with pilot light
A switch with a neon or LED indicator, such as a switch for an immersion heater.
IEC 60617
Push button
A push button on a layout drawing, such as a bell push.
IEC 60617
Push button with indicator
An illuminated push button.
IEC 60617
Time switch
A time switch, such as for lighting or heating.
IEC 60617
Bell
A bell or chime.
IEC 60617
Electric clock
An electric clock, such as a slave clock run from a master clock.
No symbols match. Try a shorter word, such as "switch" or "diode".
IEC, UK and US symbols
Most of the world, including the UK, draws circuits with the symbols in IEC 60617, published here as BS EN 60617. The US grew up with its own set, IEEE 315, which was withdrawn in 2019 but is still everywhere, especially on hobby electronics, datasheets and older drawings. The ones you'll meet most are the resistor (a box in IEC, a zigzag in the US), the fuse and the logic gates. Where the two differ we show both. Use one style throughout a drawing, and if in doubt use IEC.
Circuit diagrams and wiring layouts
A circuit diagram (schematic) shows how parts connect electrically, not where they are. A wiring layout or installation drawing is a floor plan with symbols showing where sockets, switches, lights and boards go, with lines for which switch controls which light. The installation symbols at the end of this page are the IEC 60617 ones used on UK layout drawings. Designers often add their own legend, so always read the legend on the drawing you're working from.
Tips for reading and drawing them
A dot means wires are joined. Wires that cross with no dot are not joined.
Switches and contacts are drawn in their resting state: no power, nothing pressed.
Label parts with a letter and number (R1, C2, D3, Q1, K1 for relays, F1 for fuses) and put the value beside them.
Keep power going down the page: positive or line at the top, 0 V or neutral at the bottom.
To see symbols working in real circuits, try the circuit lab, where you change values and watch the circuit react, or test yourself with Name that symbol at the top of this page.
Sources
The forms of the symbols were checked against these on 28 November 2026. The drawings are our own.