Most industrial sensors, such as pressure, flow, level and temperature transmitters, send their reading as a current between 4 and 20 mA. Checking that current normally means breaking the loop and putting a meter in series, which can upset the process. A milliamp process clamp meter reads the loop current by clamping around the wire, so the loop keeps running.
Why 4 to 20 mA?
A current loop isn't affected by the resistance of long cables, because the transmitter forces the same current all the way round. Using 4 mA, not 0 mA, as the bottom of the scale means a reading of 0 mA reveals a broken wire or a dead transmitter. The live zero also leaves enough current to power two-wire transmitters from the loop itself.
To convert a loop current to a percentage of the measured range: percent = (I − 4) ÷ 16 × 100. So 12 mA is 50%, and 8 mA is 25%.
Why an ordinary clamp meter won't do
A general-purpose clamp meter is built for amps and usually resolves 10 mA or 100 mA at best, which is coarse compared with the whole 16 mA span of a loop. A process clamp resolves 0.01 mA and is accurate to about 0.2% of reading on the 4 to 20 mA range.
What to look for
- Measure only, or source and simulate as well. Measuring tells you what the loop is doing. Sourcing lets the meter supply a known current to test a controller input or a valve positioner. Simulating lets it act as a two-wire transmitter in a loop powered by something else.
- Loop power. A built-in 24 V supply lets you power and test a transmitter on the bench, with no other kit.
- Conductor size. The jaws are small, built for instrument cable cores. The Fluke 772's clamp takes conductors up to 4.5 mm across.
- Interference. Because the meter is reading tiny magnetic fields, keep the jaws away from power cables carrying large currents, and follow the maker's zeroing instructions.
Fluke 771, 772 and 773 compared
| Feature | Fluke 771 | Fluke 772 | Fluke 773 |
|---|---|---|---|
| Clamp measurement, 0 to 20.99 mA | ±(0.2% + 5 counts) | ±(0.2% + 5 counts) | ±(0.2% + 5 counts) |
| Clamp measurement, 21 to 100 mA | ±(1% + 5 counts) | ±(1% + 5 counts) | ±(1% + 5 counts) |
| In-series measurement, 0 to 24 mA | No | Yes, ±(0.2% + 2 counts) | Yes, ±(0.2% + 2 counts) |
| Source mA (up to 24 mA into 1 kΩ) | No | Yes | Yes |
| Simulate a transmitter (up to 50 V DC loop) | No | Yes | Yes |
| 24 V loop power | No | Yes | Yes |
| Measure DC volts (0 to 30 V) | No | No | Yes |
| Source DC volts (0 to 10 V) | No | No | Yes |
| Scaled mA output to a logging meter | No | No | Yes |
All three resolve 0.01 mA and share the same IP40 rating and −10 to 50 °C operating range. Figures are from Fluke's datasheet for the 771, 772 and 773.
Which one?
- Fluke 771 if you only need to read loop currents during fault-finding. It's the simplest and lightest.
- Fluke 772 if you commission or calibrate loops. Sourcing, simulating and loop power cover most instrument technician jobs.
- Fluke 773 if you also work with 0 to 10 V signals, or want to log a loop over time through another meter.
Need a general-purpose meter too? See our multimeter guide. Our guide to ADCs explains how a microcontroller can read a 4 to 20 mA signal through a precision resistor: 250 Ω turns 4 to 20 mA into 1 to 5 V.